5.0 SPECIFICATIONS

Specifications

Maximum System Voltage

Operating DC Voltage Range

Maximum DC Operating Current

Maximum Array Short Circuit Current (DC)

Operating AC Voltage Range

Operating Frequency Range

Nominal AC Output

Voltage

Normal Output Frequency

Maximum Continuous Output AC Current

Maximum Output Fault Current (AC)

Output Overcurrent Protection

Peak Output Power

Peak Efficiency at @ 40°C Ambient Temperature

Enclosure

Dimensions (WxDxH)

Weight

Cooling

Relative Humidity

Ambient Temperature Range

Environmental Rating

Listings

 

 

 

 

 

 

 

PVP1800

 

 

PVP2800

 

 

 

 

 

 

 

 

360VDC

 

 

450VDC

 

 

 

 

 

 

 

 

120-360VDC

 

 

208: 180VDC-390VDC

 

 

 

 

240: 200VDC-390VDC

 

 

 

 

 

 

 

15A

 

 

15A

 

 

 

 

 

 

 

 

15A

 

 

15A

 

 

 

 

 

 

 

 

106V-132V

 

 

208: 183V-229V

 

 

 

 

240: 211V-264V

 

 

 

 

 

 

 

59.3Hz-60.5Hz

 

 

59.3Hz-60.5Hz

 

 

 

 

 

 

 

 

120V

 

 

208V or 240V

 

 

 

 

 

 

 

 

60Hz

 

 

60Hz

 

 

 

 

 

 

 

 

15A

 

 

14A

 

 

 

 

 

 

 

 

15A

 

 

15A

 

 

 

 

 

 

 

 

20A

 

 

20A

 

 

 

 

 

 

 

 

1800W

 

 

2800W

 

 

 

 

 

 

 

95%

 

97.6%

 

 

 

 

 

 

 

 

Aluminum-NEMA 3R to UL

 

 

Aluminum-NEMA 3R to UL

 

 

50 Standards

 

 

50 Standards

 

 

13.1” x 6.5” x 19.75”

 

 

15” x 7.5” x 21.75”

 

 

46lbs

 

 

74lbs

 

 

 

 

 

 

 

 

Natural Convection

 

 

Natural Convection

 

 

 

 

 

 

 

 

0% to 100% Condensing

 

 

0% to 100% Condensing

 

 

 

 

 

 

 

 

-25°C to +40°C

 

 

-25°C to +40°C

 

 

 

 

 

 

 

 

Conformal Coating per UL

 

 

Conformal Coating per UL

 

 

Standards

 

 

Standards

 

 

UL 1741, IEEE 519, IEEE

 

 

UL 1741, IEEE 519, IEEE

 

 

929, NEC 690

 

 

929, NEC 690

 

 

 

 

 

 

 

PV Powered LLC

21

18-28-405