Rheem 9 Kw Thru 36 Kw manual Table A - Electrical Characteristics, Table B - Recovery Capacities

Models: 9 Kw Thru 36 Kw

1 4
Download 4 pages 20.1 Kb
Page 3
Image 3
TABLE A – ELECTRICAL CHARACTERISTICS

TABLE A – ELECTRICAL CHARACTERISTICS

 

 

 

 

 

FULL LOAD CURRENT

 

INPUT

NO. OF

ELEMENT

 

 

 

IN AMPERES

 

208 VOLTS

 

240 VOLTS

600 VOLTS

KW

ELEMENTS

WATTAGE

 

PHASE

 

PHASE

PHASE

 

 

 

 

 

 

 

1

3

 

1

3

1

3

9

3

3000

43

25

 

38

22

9

 

 

 

 

 

 

 

 

 

 

12

3

4000

58

33

 

50

29

12

 

 

 

 

 

 

 

 

 

 

15

3

5000

72

42

 

63

36

15

18

3

6000

87

50

 

75

43

18

 

 

 

 

 

 

 

 

 

 

24

6

4000

116

67

 

100

58

23

 

 

 

 

 

 

 

 

 

 

30

6

5000

144

84

 

125

73

29

36

6

6000

173

100

 

150

87

35

 

 

 

 

 

 

 

 

 

 

TABLE B – RECOVERY CAPACITIES

Recovery in U.S. Gallons/Hr. (GPH) and Liters/Hr. (LPH) at Various Temperature Rises

 

INPUT

EQUIVALENT

 

40°F

50°F

60°F

70°F

80°F

90°F

100°F

110°F

120°F

130°F

140°F

 

KW

BTU/HR.

UNITS

(22°C)

(28°C)

(33°C)

(39°C)

(45°C)

(50°C)

(56°C)

(61°C)

(67°C)

(72°C)

(78°C)

 

9

30,709

GPH

93

74

62

53

47

41

37

34

31

29

27

 

 

 

 

LPH

352

282

235

201

176

157

141

128

117

108

101

 

12

40,946

GPH

124

99

83

71

62

55

50

45

41

38

35

 

 

 

 

LPH

470

376

313

268

235

209

188

171

157

145

134

 

15

51,183

GPH

155

124

103

89

78

69

62

56

52

48

44

 

 

 

 

LPH

587

470

391

335

294

261

235

213

196

181

168

 

18

61,420

GPH

186

149

124

106

93

83

74

68

62

57

53

 

 

 

 

LPH

705

564

470

403

352

313

282

256

235

217

201

 

24

81,893

GPH

248

199

165

142

124

110

99

90

83

76

71

 

 

 

 

LPH

939

751

626

537

470

417

376

342

313

289

268

 

30

102,366

GPH

310

248

207

177

155

138

124

113

103

95

89

 

 

 

 

LPH

1174

939

783

671

587

522

470

427

391

361

335

 

36

122,839

GPH

372

298

248

213

186

165

149

135

124

115

106

 

 

 

 

LPH

1409

1127

939

805

705

626

564

512

470

434

403

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SAMPLE SPECIFICATIONS (For Trade Reference Only)

Water Heater shall be Rheemglas Commercial Electric Model _____________ having an input of ________KW

and a recovery rate of ______________GPH at a __________° temperature rise, and equipped for ________ volt,

________ phase operation. Tank shall be lined with a double coating of exclusive Rheemglas high temperature

glass formula and furnished with rigidly supported anode rods. Tank shall be designed for 150 PSI working pres- sure and be approved-listed and constructed in accordance with Canadian Electrical Codes. Tank shall be com- pletely insulated with R-Foam®Insulation having a minimum insulation factor of R-16. Water heater shall be equipped with ”screw-in” immersion elements, surface thermostat, and manual reset high temperature limit control. Large terminal block that accepts either CU or AL field connect wire, plus grounding screw for attaching an equipment grounding conductor.

LIMITED WARRANTY

This product features a three year limited warranty against tank leaks. Please refer to Commercial Warranty Information brochure for complete warranty information.

Page 3
Image 3
Rheem 9 Kw Thru 36 Kw manual Table A - Electrical Characteristics, Table B - Recovery Capacities, Limited Warranty