Medium Duty Gas continued.
RECOVERY CAPACITIES Recovery in U.S. Gallons/Hr. (GPH) at various temperature rises
| MODEL NUMBER | INPUT (BTU/HR.) | 40°F | 50°F | 60°F |
| 70°F | 80°F | 90°F | 100°F | 110°F | 120°F | 130°F | |
|
| |||||||||||||
| 50,000 | 115 | 92 | 77 |
| 66 | 58 | 51 | 46 | 42 | 38 | 35 |
| |
| 45,000 | 104 | 83 | 69 |
| 59 | 52 | 46 | 41 | 38 | 35 | 32 |
| |
| 75,100 | 182 | 146 | 121 |
| 104 | 91 | 91 | 73 | 66 | 61 | 56 |
| |
| 65,000 | 158 | 126 | 105 |
| 90 | 79 | 70 | 63 | 57 | 53 | 48 |
| |
| 80,000 | 194 | 155 | 129 |
| 111 | 97 | 86 | 78 | 71 | 65 | 60 |
| |
| 76,000 | 184 | 147 | 123 |
| 105 | 92 | 82 | 74 | 67 | 61 | 57 |
| |
| Recovery rating is based on recovery efficiencies obtained in a CSA certified laboratory. | N = Low NOx |
|
|
|
|
|
|
MAXIMUM DELIVERY Delivery in U.S. Gallons. (Includes useable storage and recovery for indicated times)
| MODEL | GALLON | INPUT | TEMP. |
| 5 | 10 | 15 | 20 | 30 | 45 | 60 | 120 | 180 | Min. to Rec. | |
| NUMBER | CAPACITY | (BTU/HR.) | RISE | UNITS | Min. | Min. | Min. | Min. | Min. | Min. | Min. | Min. | Min. | Contents | |
| 60 | 50,000 | 100 °F | GAL | 46 | 50 | 54 | 57 | 65 | 77 | 88 | 134 | 180 | 78 |
| |
| 60 | 45,000 | 100 °F | GAL | 45 | 49 | 52 | 56 | 63 | 73 | 84 | 125 | 166 | 87 |
| |
| 75 | 75,100 | 100 °F | GAL | 59 | 65 | 71 | 77 | 89 | 107 | 125 | 198 | 271 | 62 |
| |
| 75 | 65,000 | 100 °F | GAL | 57 | 63 | 68 | 74 | 84 | 100 | 116 | 179 | 242 | 71 |
| |
| 100 | 80,000 | 100 °F | GAL | 77 | 83 | 89 | 96 | 109 | 128 | 148 | 225 | 303 | 77 |
| |
| 100 | 76,000 | 100 °F | GAL | 76 | 82 | 88 | 95 | 107 | 125 | 144 | 217 | 291 | 81 |
|
DIMENSIONAL INFORMATION
|
|
|
|
|
|
|
|
|
|
| CLEARANCE TO |
| APPROX. | |||
| MODEL |
| A | B | C | D | E | F | G |
| COMBUSTIBLES |
| SHIPPING | |||
| NUMBER | UNITS | SIDE |
| FRONT |
| TOP | WEIGHT |
| |||||||
| inches | 62 | 58 | 23 | 4 | 8 | 1 |
| 3 |
| 2 | 180 lbs |
| |||
| inches | 64 | 60 | 4 | 11 | 1 |
| 3 |
| 2 | 320 lbs. |
| ||||
| inches | 11 | 4 | 15 | 1 |
| Alcove |
| 12 | 410 lbs. |
Recommended Specifications:
Water heater(s) shall be model ______________,
manufactured by
of _______ GPH at a 100°F temperature rise.
Water heater(s) shall have a storage capacity of
_________ gallons. Water heater(s) shall have
the AGA seal of certification and be factory equipped with an AGA/ASME rated temperature and pressure relief valve. Tank(s)shall have a coating of high temperature porcelain enamel and furnished with a magnesium anode rod rigidly supported and a full port, full flow brass drain valve. Water heater(s) shall meet or exceed the energy factor requirements of ASHRAE. Tanks
F
E
3/4" N.P.T.
RELIEF
VALVE
OPENING
| C | SIDETAPS | A |
|
| ||
|
| B | |
A B |
| (75 GAL. | |
| G MODEL |
| |
| 1/2" | ONLY) |
|
|
|
|
F
E
3/4" T & P
HOT & COLD
C |
|
1/2" GAS | G |
CONNECTION |
|
shall have a working pressure rating of 150 psi, and shall be completely factory assembled, including a pressure regulator properly adjusted for operation on ___________ gas. Controls will
be arranged for safety shutoff in event of pilot failure. Complete unit shall be insulated with rigid polyurethane foam insulation. Water heater(s) shall be covered by a three year limited warranty against tank leaks.
Limited Warranty:
This product features a three year limited warranty against tank leaks. Please refer to Commercial Warranty Information brochure for complete warranty information.
D | D | 2" |
|
| |
|
| |
SIDE TAPS ON 75 GAL. | WATER CONNECTIONS | |
MODEL ONLY |
| ARE 1" NPT |
ARE 3/4" NPT
ARE 1" NPT
In keeping with its policy of continuous progress and product improvement,
Rheem Water Heating • 101 Bell Road, Montgomery, Alabama
PRI NTED IN U. S. A | 11/ 07 WP | F O RM NO . |