CONNECTIONS – ELECTRICAL
31
POWER FLUE EXTERNAL CONTROLS – 24 HOUR OPERATION
Notes:
1. Power source for the water heater, fan and control circuit must be from the same
circuit.
2. R 1 monitors return signal.
3. R2 monitors alarm signal.
4. T1 to be set for 20-30 seconds.
5. Use SPO with round earth terminal. Water heater supply cord must be changed to
suit.
6. Meets requirements of Clause H.2.2.6 of AS5601 – 2004, providing lockout in the
event of flue product flow failure.