Operating instructions Rinnai
6
!
!
i
DANGER
WARNING
NOTICE
Should overheating occur or the gas supply fail to shut off, do not turn off or disconnect the electrical supply to the pump. Instead, shut off the gas supply at a location external to the appliance.
Protection for corrosion
Do not use any sprays, chlorine containing agents, solvents, paint etc. around the boiler or around the air intake supply entrance of the boiler. These substances have negative influences on the boiler and can lead to corrosion resulting in failure of the boiler.
Products to avoid present in boiler room and/or around combustion air intake Spray cans containing
Chlorinated waxes and/or cleaners Swimming pool chemicals based on chlorine Calcium chloride used for thawing Sodium chloride used for water softening Refrigerant leaks
Paint or varnish removers Hydrochloric acid/muriatic acid Cements and glues
Antistatic fabric softeners used in clothes dryers
Adhesives used to fasten building products and other similar products
Areas likely to have contaminants
Dry cleaning/laundry areas and establishments
Swimming pools
Metal fabrication plants
Beauty shops
Refrigeration repair shops
Photo processing plants
Auto body shops
Plastic manufacturing plants
Furniture refinishing areas and establishments
New building construction
Remodeling areas
Garages with workshops
Checking the water pressure
Check the water pressure in the central heating installation regularly.
Use only potable water for filling. Additives only after clearance by Rinnai. Contact your installer in case of doubt.