SECTION 2: SPECIFICATIONS

ROBERTS GORDON® ULTRAVAC™ CONTROLLER INSTALLATION MANUAL

SECTION 2: SPECIFICATIONS

2.1ROBERTS GORDON® ULTRAVAC™ Controller 2.1.1 Standard Enclosure

Construction: 16 gauge painted steel, hinged door, removable knockouts provided.

Dimensions: W x H x D

(in): 14.7 x 17.7 x 3.5

(cm): 37.3 x 45.0 x 8.9

2.1.2 Electrical

Power Supply: 120 V (+/- 10%) 1 Ø, 60 Hz

UL Standard: UL 916 / C22.2 No. 205-M1983

Universal Inputs: Eight Universal Inputs

Thermistor

0-10 Vdc

4-20m A Resistance Dry contact

Analog Output:

One Analog Output 0-10 Vdc

Digital Inputs:

Digital Inputs: Timed, dry contact

Digital Outputs:

Eight Digital Output: Single Pole 3 A 120 Vac

Ports:

RS-485 Communications Bus

RS-232 Direct Connect Bus

RS-232 Modem Socket

2.2ULTRAVAC™ BMS Link Controller 2.2.1 Standard Enclosure

Construction: 16 gauge painted steel, hinged door, removable knockouts provided.

Dimensions: W x H x D (in):14.7 x 17.7 x 3.5 (cm): 37.3 x 45.0 x 8.9

2.2.2 Electrical

Power Supply: 120V (+/-10%) 1 Ø, 60 Hz

Ports:

RS-485 Communications Bus

Ethernet/IP

2.3 NEMA 4 Enclosure (P/N 10080302)

Description: NEMA 4 enclosure is sold separately as an option, for ULTRAVAC™ Controller and ULTRAVAC™ BMS

16 of 62

Link Controller.

Standard enclosures are field mounted inside the NEMA 4 enclosure.

Construction: 14 gauge painted steel, hinged door with 19" (48.3 cm) x (40.6 cm) 16" window.

Dimensions:

W x H x D

 

(in): 24 x 24 x 9

 

(cm): 61.0 x 61.0 x 22.9

Protection

 

Rating:

NEMA 4, 12

2.4 Repeater

2.4.1 Standard Enclosure

Construction: Fabricated in accordance with UL specifications from code gauge steel, NEMA 1.

Finish:

Austin screw cover boxes standard

 

construction galvanized steel with

 

ANSI 61 gray polyester powder

 

coating.

Dimensions:

W x H x D

 

(in): 12 x 12 x 4

 

(cm): 30.5 x 30.5 x 10.5

2.4.2 Electrical

Power Supply: 120 V (+/- 10%) 1 Ø, 60 Hz

Ports:

RS-485 Communications Bus

RS-232 Direct Connect Bus

2.5Temperature Sensors Indoor Sensor

Dimensions:

W x H x D

 

(in): 2.75 x 4.5 x 1.15

 

(cm): 7.0 x 11.4 x 2.9

Power:

32 V DC

Operating Temperature Range:

 

32° to 158° F (0° to 70° C)

Features:

LCD temperature display, setpoint

 

adjustment, override button

Outdoor Sensor (P/N 10081501)

Dimensions:

W x H x D

 

(in): 1.4 x 5.3 x 2

 

(cm): 3.6 x 13.5 x 5.1

Operating Temperature Range:

-40° to 221° F (-40° to 5° C)