1.0" w.c. - 1.2" wc VFD Frequency Setting

SECTION 8: COMMISSIONING THE CORAYVAC® SYSTEM

Step 8.1.3 After setting end vent vacuums between 2.5" wc and 3.0" wc, while all the burners are still operating, use the down arrow button on the VFD to reduce the frequency of the output signal to the pump. Reduce the frequency of the VFD until the manometer at each of the end vents reads 1.0" wc - 1.2" wc, Make note of this frequency setting below. The frequency is found on the VFD’s LCD screen.

1.0" w.c. - 1.2" wc VFD Frequency Setting

Record Frequency Setting Here:

Step 8.1.4 Return to the PC and click the pump and zones to "OFF".

Step 8.1.5 Using the procedure described on Page 42, Section 7.1.1 through Section 7.1.5, alter the fol- lowing parameters on the VFD:Return to the PC and click the vacuum pump and three zones to "AUTO", then click exit.

Parameter

Parameter

Factory

New

Number

Name

Default

Setting

 

 

 

 

P01

Line Voltage

01

01

 

 

 

 

P03

Start Method

01

05

 

 

 

 

P05

Standard

01

(03) (0-10) Vdc

 

Speed

 

(04) (4-20) mA

 

Source

 

 

 

 

 

 

P44

Password

225

Any #

 

 

 

000-999

 

 

 

 

P45

Speed at

0.0Hz

Frequency

 

Minimum

 

Setting noted

 

Signal

 

on Page 44,

 

 

 

Section 8.1.2

 

 

 

 

P46

Speed at

60.0Hz

Frequency

 

Maximum

 

Setting noted

 

Signal

 

on Page 44,

 

 

 

Section 8.1.2

 

 

 

 

47 of 62

Page 53
Image 53
Roberts Gorden 10081601NA Rev H 12/11 1.0 w.c. - 1.2 wc VFD Frequency Setting, Record Frequency Setting Here, Parameter