SECTION 5: COMMUNICATIONS

5.5 Communications Between Multiple ROBERTS GORDON® ULTRAVAC™ Controllers

If more than one ROBERTS GORDON® ULTRAVAC™ Controller is installed in a building, the controllers’ RS-485 communications must be wired in series. See Page 35, Figure 20. Connect the RS-485 terminal on controller #1 to the RS-485 terminal on controller #2 and so on in a daisy chain fashion. For communication cable requirements, See Page 22, Section 3.3

From a PC, by dialing into the modem on controller #1 or by connecting to controller #1 via RS-485 converter or TCP/IP communication module, the

system status and settings can be viewed for any of the controllers on the network.

The control board identification dip switch must be set on each ROBERTS GORDON® ULTRAVAC™ Controller. See Page 35, Figure 20 for dip switch settings. Contact Roberts-Gordon or your ROBERTS GORDON® independent distributor, if more than 20 controllers are connected.

FIGURE 20: Communications Between Multiple Controllers

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controller/Address

Dip Switch Order (1,2,3,4,5,6,7,8)

Number

 

 

Values (1=ON, 0=OFF)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 (Central Controller)

10000000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

01000000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

11000000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

00100000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

10100000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

01100000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

11100000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

 

00010000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

 

10010000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

01010000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controller/Address

Dip Switch Order (1,2,3,4,5,6,7,8)

Number

 

 

Values (1=ON, 0=OFF)

 

 

 

 

 

 

 

 

 

11

 

11010000

 

 

 

 

 

 

 

 

 

12

 

00110000

 

 

 

 

 

 

 

 

 

13

 

10110000

 

 

 

 

 

 

 

 

 

14

 

01110000

 

 

 

 

 

 

 

 

 

15

 

11110000

 

 

 

 

 

 

 

 

 

16

 

00001000

 

 

 

 

 

 

 

 

 

17

 

10001000

 

 

 

 

 

 

 

 

 

18

 

01001000

 

 

 

 

 

 

 

 

 

19

 

11001000

 

 

 

 

 

 

 

 

 

20

 

00101000

 

 

 

 

 

 

 

 

 