SECTION 5: PUMP INSTALLATION
FIGURE 9: Condensate Check Valve
1" NPT threaded hole. Use 1" x ¾" reducer.
(not supplied)
Copper or galvanized pipe between pump and condensate
valve.
3/4" female
Condensate | flow |
Valve | |
Assembly |
|
3/4" female
Wall | Description | Part Number |
| Condensate Valve Assembly | 01327001 |
36" Minimum vertical drop between pump and condensate valve assembly.
Must be connected to a drain system in accordance with local codes.
FIGURE 10: Condensate Tee - Discharge Side
| 4"(100 mm) |
|
Flex Boot | Minimum | Tee |
|
|
| Approved | |
Drain Cap | Thimble | |
(if applicable) | ||
| ||
| 1"(25 mm) | |
| P.V.C |
5.3 Condensate Trap and Condensate Tee
The condensate trap assembly (optional) (P/N 01327001), should be installed on the inlet side of the
It is possible to eliminate the condensate trap assem- bly on the pump if the
The condensate trap assembly in the discharge line can be eliminated if the discharge line is horizontal through the wall and pitched down at least one inch per foot. A condensate trap on the discharge side is required if there is a vertical rise in the discharge line.