4 Type Test Specifications

Electrical Safety

Levels

 

Comments

Dielectric Withstand

2 kV rms for 1 minute

 

ANSI/IEEE C37.90 (1989)

 

 

 

 

IEC 60255-5 (Section 6)

High Voltage Impulse

5 kV peak

 

IEC 60255-5 (Section 8)

Insulation Resistance

500 VDC for 1 minute

 

IEC 60255-5 (Section 6

 

 

 

 

 

Electrical Environment

Levels

 

Comments

High Frequency Disturbance

2.5 kV @ 1MHz for 2s

 

ANSI/IEEE C37.90.1

(Oscillatory)

 

IEC 60255-22-1

 

 

 

IEC Surge

4 kV / 2 kV

 

IEC 61000-4-5

 

(Level 4)

 

 

 

 

IEC Fast Transient

2 kV / 1 kV

 

IEC 61000-4-4

 

(Level 4)

 

 

 

 

ANSI/IEEE Fast Transient

4 kV

 

ANSI/IEEE C37.90.1

IEC Radiated RFI Immunity

10 V/m

 

IEC 61000-4-3

ANSI/IEEE Radiated RFI

35 V/m

 

ANSI/IEEE C37.90.2

Immunity

 

 

 

 

 

ESD

15 kV (air discharge)

 

IEC 61000-4-2

(Electrostatic Discharge)

8 kV (contact)

 

(Level 4)

 

 

 

 

 

Atmospheric Environment

Levels

 

 

Comments

Temperature (Dry Cold)

-40°C

 

 

IEC 60068-2-1

 

Test Ad: 16 hrs @ -40°C

 

 

 

Temperature (Dry Heat)

85°C

 

 

IEC 60068-2-2

 

Test Bd: 16 hrs @ 85°C

 

 

 

 

95%

 

 

IEC 60068-2-30

Humidity

 

Test Db: 6 cycles, 55°C, 95%

Non-condensing

 

 

 

 

Humidity

 

 

 

 

15

2006 RuggedCom Inc. All rights reserved

Rev101

Page 15
Image 15
RuggedCom RMC40 manual Type Test Specifications, Electrical Safety Levels Comments, Iec, 95%