Air Purge

Be sure that all valve cocks are closed.

The air in the indoor unit and in the pipe must be purged. If air remains in the refrigeration pipes, it will affect the compressor, reduce to cooling capacity and could lead to a malfunction.

Use Vacuum Pump as shown at the figure.

1.Connect each assembly pipe to the appropriate valve on the outdoor unit and tighten the flare nut.

2.Connect the charging hose of low pressure side of manifold gauge to the packed valve having a service port as shown at the figure.

3.Open the valve of the low pressure side of manifold gauge counter-clockwise.4.Purge the air from the system using vacuum pump for about 10 minutes.-Close the valve of the low pressure side of manifold gauge clockwise.-Turn off the vacuum pump.-Make sure that pressure gauge show -0.1MPa(-76cmHg) after about 10 minutes.-This procedure is very important in order to avoid gas leak.-Remove the hose of the low pressure side of manifold gauge.

5.Set valve cork of both liquid side and gas side of packed valve to the open position.

6.Mount the cap and the needle valve cap to the valve (see the below illustration), and tighten them at the torque of 183kgf•cm with a torque wrench.

7.Check for gas leakage.

-At this time, especially check for gas leakage from the 3-way valve’s stem nuts, and from the service port cap.

Gas pipe

 

 

 

 

side

OUTDOOR UNIT

 

 

 

Liquid

 

 

Indoor unit

pipe side

A

 

 

 

 

 

 

B

 

Liquid pipe side

Gas pipe side

 

 

 

 

Flare nut

Vacuum

 

 

 

 

 

 

 

Valve cock

Pump

3-way valve

3-way valve

 

Cap

 

 

 

 

Needle valve

 

Outdoor unit

 

 

 

 

 

cap

 

 

 

installation part _43