Space Requirements for Outdoor Unit

If using a multi system, install as described in the installation manual supplied with the outdoor unit.

When installing 1 outdoor unit

Figure Description

 

 

 

Top view

 

Side view

 

 

 

 

 

Air intake

Air outlet

 

 

Air intake

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air outlet

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

,

Air flow direction.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Unit : mm)

When the air outlet is opposite the

When the air outlet is towards the

When 3 sides of the outdoor unit are

 

wall

 

 

 

wall

 

 

 

 

blocked by the wall

ENGLISH

300 or more

The upper part of the outdoor unit and the air outlet is towards the wall

2000 or more

or more

 

1500

1500 or more

The upper part of the outdoor unit and the air outlet is opposite the wall

500 or more

300 or more

 

300 or more

150 or more

600 or more

When the walls are blocking front and the rear side of the outdoor unit

1500 or 300 or more more

When installing more than 1 outdoor unit

 

(Unit : mm)

When the air outlet is towards the wall

When 3 sides of the outdoor unit are blocked by the wall

1500 or more

300 or more

300 or more

600 or more 600 or more 600 or more

25

Page 25
Image 25
Samsung AQV12PWCXCEE, AQV09PWCNEUR Space Requirements for Outdoor Unit, When installing 1 outdoor unit, Top view Side view