Purging the connected pipes

Important information regulation regarding the refrigerant used

This product contains fluorinated greenhouse gases covered by the Kyoto Protocol.

Do not vent gases into the atmosphere.

1.Please fill in with indelible ink,

the factory refrigerant charge of the product,

the additional refrigerant amount charged in the field and

+the total refrigerant charge. on the refrigerant charge label supplied with the product.

a. Factory refrigerant charge of the product: see unit name plate

b.Additional refrigerant amount charged in the field (Refer to the above information for the quantity of refrigerant replenishment.)

c.Total refrigerant charge

d.Refrigerant cylinder and manifold for charging

Refrigerant type

GWP value

R410A

1975

GWP=Global Warming Potential

Contains fluorinated greenhouse gases covered by the Kyoto Protocol.

Indoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

d

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

a

 

 

 

 

 

 

 

 

 

 

Outdoor unit

= (

 

 

) kg

 

 

 

 

 

 

 

= (

 

 

) kg += (

 

) kg

 

 

 

b

 

 

 

 

c

• The filled-out label must be adhered in the proximity of the product charging port (e.g. onto the inside of the stop valve cover).

Charging the refrigerant under conditions of liquid by using a liquid pipe

R410A is a mixed type of refrigerant. It is necessary for recharging under conditions of liquid. When recharging refrigerant from the refrigerant cylinder to the equipment, follow the instructions below.

1.Before recharging, check whether the cylinder has a siphon or not. There are two ways to recharge the refrigerant.

Cylinder with siphon

Cylinder without siphon

siphon

Charge the refrigerant standing the cylinder upright.

Charge the refrigerant turning the cylinder upside down.

• If R410A refrigerant is charged with gas, the composition of the charged refrigerant changes and the

characteristics of the equipment vary.

During the measuring operation of refrigerant quantity added use an electronic balance.

If cylinder doesn’t have syphon, upset it.