Fixing the installation plate

2. Fix the indoor unit.

If you fix the indoor unit on a wall

(1) Fix the installation plate to the wall giving attention to the weight of the indoor unit.

• If you mount the plate to a concrete wall using plastic anchors, make sure that

gaps between the wall and the plate, created by projected anchor, is less than 20mm.

Plastic

 

 

Anchor

 

Wall

 

<20mm

 

 

If you fix the indoor unit on a window frame

(1)Determine the positions of the wooden uprights to be attached to the window frame.

(2)Attach the wooden uprights to the window frame giving attention to the weight of the indoor unit.

(3)Attach the installation plate to the wooden upright using tapping screws.

If you fix the indoor unit on a gypsum board

(1)Use stud finder to find out locations of the studs.

(2)Fix the plate hanger on two studs.

• Search for other spots if there are less than two studs, or the distance between the studs are different from the plate hanger.

Fix the installation plate without inclining to one side.

Make sure that a wall can withstand the weight of the product. If you install the product in a place where it is not

strong enough to withstand the product weight, the unit could fall and cause injury.

Connecting the assembly cable

If using a multi system, install as described in the installation manual supplied with the outdoor unit.

Cable specification

Model

Power cable

Interconnection cable

Type GL

 

 

 

 

 

 

 

 

 

AQV09/12PC

3G, 1.5mm² H07RN-F

4G, 1.5mm² H07RN-F

20A

AQV09/12PB

3G, 2.5mm² H07RN-F

3G, 1.5mm² H07RN-F

20A

2G, 0.75mm² H05RN-F

 

 

 

 

 

AQV18/24P

3G, 2.5mm² H07RN-F

3G, 1.5mm² H07RN-F

25A

2G, 0.75mm² H05RN-F

 

 

 

 

 

• Connect the power cable to the auxiliary circuit breaker. If every pole fails to connect to

the power supply, it must be incorporated in a wire with a contact opening of ≥3mm.

Connecting the cable

When you install the unit, make first refrigerant connections and then electrical connections. Connect the air conditioner to grounding system before performing the electrical connection. If unit is uninstalled, first disconnect electrical cables, then refrigerant connections.

If the outdoor unit is more than 5 meters away from the indoor unit, you must extend the cable. The maximum length of the cable is 15(09/12)/20(18/24) meters.

1. Extend the assembly cable if necessary.

• Do not connect two or more different cables to extend the length. It may cause fire.