Samsung AR09MSFTBWKNTV, AR30MSFTBWKNTV, AR24MSFTBWKNTV manual Pumping down for removing the product

Models: AR12MSFTBWKNTV AR18MSFTBWKNTV AR24MSFTBWKNTV AR09MSFTBWKNTV AR30MSFTBWKNTV

1 48
Download 48 pages 36.77 Kb
Page 48
Image 48

WARNING

After installing the product, be sure to perform leak tests on the piping connections. Before pumping down refrigerant to inspect or relocate the outdoor unit, be sure to stop the compressor and then remove the connected pipes.

––Do not operate the compressor while a valve is open due to refrigerant leakage from a pipe or an unconnected or incorrectly connected pipe. Failure to do so may cause air to flow into the compressor and too a high pressure to develop inside the refrigerant circuit, leading to an explosion or product malfunction.

1Shut off the liquid valve with the Allen wrench.

2Turn on the air conditioner in cooling with fan operating at high velocity. (Compressor will immediately start, provided 3 minutes have elapsed since the last stop.)

3After 2 minutes of operation, shut the suction valve with the same wrench.

4Turn off the air conditioner and switch mains supply off.

5Disconnect tubing. After disconnection, protect valves and tubing ends from dust.

CAUTION

Compressor damage may occur if the compressor is run at a negative suction pressure.

Pumping down for removing the product

1Hold down the (Power) button on the indoor unit for 5 seconds. Beep sounds immediately to indicate that the product is ready for pump down procedure.

2Let the compressor run for more than 5 minutes.

3Release the valve caps on High and Low pressure side.

4Use L-wrench to close the valve on the high pressure side.

5After approximately 1 minute, close the valve on the low pressure side.

6Stop operation of the air conditioner by pressing

the (Power) button on the indoor unit or remote control.

7Disconnect the pipes.

 

1

 

1 minute

Liquid service port

Gas service port

<High pressure>

<Low pressure>

2

Off

Installation

English 47

Page 48
Image 48
Samsung AR09MSFTBWKNTV, AR30MSFTBWKNTV, AR24MSFTBWKNTV, AR12MSFTBWKNTV, AR18MSFTBWKNTV Pumping down for removing the product