Mini ECOi Multi Split VRF Heat Pump

CHX (R) 03652 / CHX (R) 05252

Key Features:

*Single Phase 208/230 volts

CHXseries

SANYO’s Mini ECOi is suited for numerous commercial and premium residential applications.

*One Outdoor Unit Connects As Many As 9 Indoor Units (50%-130% ratio of indoor to outdoor capacity)

*Inverter Driven Twin Rotary Compressor

*Operating Range (Outdoor Ambient)

-Cooling 14 FDB to 113 FDB

-Heating -4 FWB to 59 FWB

*Ultra Quiet Operation As Low As 51dB(a)

*Variable Speed DC Fan Motor

*Piping:

-656 Feet - Maximum Total Liquid Line

-164 Feet - Maximum Vertical Between Indoor and Outdoor (Outdoor Above Indoor) -131 Feet - Maximum Vertical Between Indoor and Outdoor (Outdoor Below Indoor)

*Defrost control, Reverse cycle, microprocessor control

*External finish: Galvanized steel plate with powder paint

*Refrigerant control: Electronic expansion valve

SANYO OUTDOOR

DESCRIPTION

CHX (R) 03652

 

CHX (R) 05252

POWER SOURCE

208-230V/1PH/60Hz

 

208-230V/1PH/60Hz

 

 

 

 

Performance

Ducted Non-Ducted Mix

 

Ducted Non-Ducted Mix

Cooling capacity

40,000

39,000

39,000

BTU/H

51,500

52,000

51,500 BTU/H

SEER

14.20

16.40

15.30

 

14.6

17.3

16

Heating capacity

40,500

42,500

41,500

BTU/H

57,500

58,000

58,500 BTU/H

HSPF

8.20

9.60

8.90

 

7.7

9.5

8.6

Air circulation (Hi)

 

3,530 CFM

 

 

3,530 CFM

 

 

 

 

 

 

 

 

ELECTRICAL RATINGS

Cooling

 

HEATING

 

Cooling

 

HEATING

Voltage rating

208 / 230 V

208 / 230 V

 

208 / 230 V

 

208 / 230 V

Available voltage range

187—253 V

187—253 V

 

187—253 V

187—253 V

Running amperes

14.6 / 13.6 A

14.6 / 13.6 A

 

23.5 / 21.9 A

23.5 / 21.9 A

Max. Running amperes

23.6 / 23.6 A

23.6 / 23.6 A

 

28 / 28 A

 

28 / 28 A

Power input

2.76 / 2.76 Kw

2.88 / 2.88 Kw

 

4.57 / 4.57 Kw

4.58 / 4.58 Kw

Max. Power input

4.85 / 4.85 Kw

4.85 / 4.85 Kw

 

5.72 / 5.72 Kw

5.7 2 / 5.72 Kw

Min. circuit ampacity

 

 

18 A

 

 

 

29 A

Max circuit ampacity

 

 

30 A

 

 

 

50 A

 

 

 

 

 

 

 

 

REFRIGERANT TUBING

 

 

 

 

 

 

 

Limit of tubing length

 

 

656 ft

 

 

 

656 ft

Limit of elevation difference

Outdoor unit is higher than indoor unit: 164

Outdoor unit is higher than indoor unit: 164

Between the 2 units

Outdoor unit is lower than indoor unit: 131

Outdoor unit is lower than indoor unit: 131

 

 

 

 

 

 

 

 

Refrigerant tube diameter

 

 

 

 

 

 

 

Liquid tube in.

 

 

3/8"

 

 

 

3/8"

Gas tube in.

 

 

5/8"

 

 

 

3/4"

 

 

 

UNIT DIMENSIONS

Height/ Width/ Depth/ Net Weight

Height/ Width/ Depth/ Net Weight

Inches (") / lbs.

49”/ 37”/ 14”/ 229 lbs.

 

49”/ 37”/ 14”/ 229 lbs.

Shipping weigh / volume

247 lbs. / 19.8 ft.3

 

 

247 lbs. / 19.8 ft.3

 

External air temp. Operation range

Cooling:14 to 113 (DB)/Heating: -4 to 59 (WB)

Cooling:14 to 113 (DB)/Heating: -4 to 59 (WB)

 

 

 

 

 

 

 

 

*NOTE: *(R) in Model # indicates Salt Protection - Special Order