WCHDXseries

W 2-Way ECOi VRF Heat Pumps combined units

DESCRIPTION

WCHDX

WCHDX

WCHDX

WCHDX

21663

24063

26463

28863

 

includes (3)

includes (2)

includes (1)

includes (3)

 

CHDX07263

CDDX07263 and (1)

CHDX07263 and (2)

CHDX09663

 

 

CHDX09663

CHDX09663

 

Performance

 

 

 

 

Cooling capacity: BTU/H

216,000

240,000

264,000

288,000

Power input: kW

15.84

18.25

20.66

23.07

Heating capacity: BTU/H

243,000

270,000

297,000

324,000

Power input: kW

17.37

20.18

22.99

25.8

 

 

 

 

 

Cooling Mode Nominal Conditions

 

 

 

 

Indoor: °F WB/ °F DB

80/67

80/67

80/67

80/67

Outdoor: °F DB

95

95

95

95

Pipe Length: Feet

25

25

25

25

Level Difference: Feet

0

0

0

0

 

 

 

 

 

Heating Mode Nominal Conditions

 

 

 

 

Indoor: °F DB

70

70

70

70

Outdoor: °F DB/ °F WB

47/43

47/43

47/43

47/43

Pipe Length: Feet

25

25

25

25

Level Difference: Feet

0

0

0

0

 

 

 

 

 

Operating Range

 

 

 

 

Cooling: °F DB

14 to 113

14 to 113

14 to 113

14 to 113

Heating: °F WB

-4 to 59

-4 to 59

-4 to 59

-4 to 59

 

 

 

 

 

Compressor

 

 

 

 

Type/Quantity

3 Inverter driven

3 Inverter driven Rotary

3 Inverter driven Rotary

3 Inverter driven

 

Rotary

& 1 fixed speed scroll

& 2 fixed speed scroll

Rotary

Capacity Control Range: %

6 - 100%

6 - 100%

6 - 100%

& 3 fixed speed scroll

 

 

 

 

6 - 100%

 

 

 

 

 

Fan

 

 

 

 

Type/Quantity

1 Propeller (ea)

1 Propeller (ea)

1 Propeller (ea)

1 Propeller

Fan Motor Output: (kW)

0.7 kW (ea)

0.7 kW (ea)

0.7 kW (ea)

0.7 kW

External Static Pressure

.04 / .25

.04 / .25

.04 / .25

.04 / .25

 

 

 

 

 

Power Supply

 

 

 

 

V/PH/Hz

208 - 230/ 3/ 60

208 - 230/ 3/ 60

208 - 230/ 3/ 60

208 - 230/ 3/ 60

Minimum Circuits Amps (MCA): (A)

78

86

94

102

Max. Overcurrent Protection (MOCP): (A)

120

125

130

135

 

 

 

 

 

Weight: (lbs)

1752

1851

1950

2049

 

 

 

 

 

Coil:

 

 

 

 

Coil Face Area:(sq. Ft.)

29.5(ea)

29.5(ea)

29.5(ea)

29.5(ea)

Number of Rows:

4(ea)

4(ea)

4(ea)

4(ea)

 

 

 

 

 

Protection Devices

 

 

 

 

High Pressure Switch/Overcurrent (CT

Yes

Yes

Yes

Yes

Method)

25 + 25 + 25

25 + 25 + 25 + 32

(2 X 25 + 32) + 25

3 X 25 + 32

Crankcase Heaters:(W)

 

 

 

 

 

 

 

 

 

Each outdoor unit requires a separate electrical FUSED DISconnecT, see individual outdoor requirements.

(R)indicates with salt protection - Special Order

*NOTE: *460 Volt Step Down Transformers (460-230) available for 6 and 8 ton condensers