3-Way ECOi VRF Heat Recovery Combined Units WCHDZseries
DESCRIPTION | WCHDZ 14463 | WCHDZ 16863 | WCHDZ 19263 | |
| includes (1) CHDZ07263 | includes (1)CHDZ07263 and | includes (1) CHDZ09663 | |
| and (1) CHDZ07263 | (1) CHDZ09663 | and (1) CHDZ09663 | |
Performance |
|
|
| |
Cooling capacity: BTU/H | 144,000 | 168,000 | 192,000 | |
Power input: kW | 10.56 | 12.97 | 15.38 | |
Heating capacity: BTU/H | 162,000 | 189,000 | 216,000 | |
Power input: kW | 11.58 | 14.39 | 17.2 | |
|
|
|
| |
Cooling Mode Nominal Conditions |
|
|
| |
Indoor: °F WB/ °F DB | 80/67 | 80/67 | 80/67 | |
Outdoor: °F DB | 95 | 95 | 95 | |
Pipe Length: Feet | 25 | 25 | 25 | |
Level Difference: Feet | 0 | 0 | 0 | |
|
|
|
| |
Heating Mode Nominal Conditions |
|
|
| |
Indoor: °F DB | 70 | 70 | 70 | |
Outdoor: °F DB/ °F WB | 47/43 | 47/43 | 47/43 | |
Pipe Length: Feet | 25 | 25 | 25 | |
Level Difference: Feet | 0 | 0 | 0 | |
|
|
|
| |
Operating Range |
|
|
| |
Cooling: °F DB | 14 to 113 | 14 to 113 | 14 to 113 | |
Heating: °F WB | ||||
|
|
|
| |
Compressor |
|
|
| |
Type/Quantity | 2 Inverter driven Rotary | 2 Inverter driven Rotary | 2 Inverter driven Rotary | |
|
| & 1 fixed speed scroll | & 2 fixed speed scroll | |
Capacity Control Range: % | 6 - 100% | 6 - 100% | 6- 100% | |
|
|
|
| |
Fan |
|
|
| |
Type/Quantity | 1 Propeller (ea) | 1 Propeller (ea) | 1 Propeller (ea) | |
Fan Motor Output: (kW) | 0.7 kW (ea) | 0.7 kW (ea) | 0.7 kW (ea) | |
External Static Pressure | .04 / .25 | .04 / .25 | .04 / .25 | |
|
|
|
| |
Power Supply |
|
|
| |
V/PH/Hz | 208 - 230/ 3/ 60 | 208 - 230/ 3/ 60 | 208 - 230/ 3/ 60 | |
Minimum Circuits Amps (MCA): (A) | 52 | 60 | 68 | |
Max. Overcurrent Protection (MOCP): (A) | 80 | 85 | 90 | |
|
|
|
| |
Weight: (lbs) | 1168 | 1267 | 1366 | |
|
|
|
| |
Coil: |
|
|
| |
Coil Face Area:(sq. Ft.) | 29.5(ea) | 29.5(ea) | 29.5(ea) | |
Number of Rows: | 4(ea) | 4(ea) | 4(ea) | |
|
|
|
| |
Protection Devices |
|
|
| |
High Pressure Switch/Overcurrent | Yes | Yes | Yes | |
(CT Method) | ||||
25 + 25 | 25 + 25 + 32 | 25 + 32 X 2 | ||
Crankcase Heaters:(W) | ||||
|
|
| ||
|
|
|
|
Each outdoor unit requires a separate electrical FUSED DISconnect, see individual outdoor requirements.
(R)indicates with salt protection - Special Order
*NOTE: *460 Volt Step Down Transformers
SANYO OUTDOOR