7UK Conditions: Cooling Indoor 23˚C DB 50% RH Outdoor 30˚C Heating Indoor 20˚C Outdoor 0˚C
Rating Conditions: Cooling Indoor 27˚C DB 19˚C WB Outdoor 35˚C DB 24˚C WB Heating Indoor 20˚C DB Outdoor 7˚C DB 6˚C WB

8

UK Conditions: Cooling Indoor 23˚C DB 50% RH Outdoor 30˚C Heating Indoor 20˚C Outdoor 0˚C
Rating Conditions: Cooling Indoor 27˚C DB 19˚C WB Outdoor 35˚C DB 24˚C WB Heating Indoor 20˚C DB Outdoor 7˚C DB 6˚C WB

Dimensions of unit combinations (ECOi 2 Way and 3 Way)

ECOi 2 Way Heat Pump VRF Inverter Systems

System example for ECOi 2 Way

Since all piping is concentrated into one
pipe shaft, you can minimise piping space
and construction labour.
If your indoor capacity load changes in the future, it ’s easy to add
on both indoor and outdoor units using the same piping.
SANYO make it possible to link outdoor
units together for a large capacity (48HP)
If indoor/outdoor units need servicing, a ball valve
(optional) cuts o non-operational units to let other
units stay running.
Connection
Concentration
Addition
System limitations
Maximum number of combined outdoor units 3
Maximum HP of combined outdoor units 48HP
Maximum number of connectable indoor units 40
Indoor/outdoor unit capacity ratio 50-130%
Maximum actual piping length 150m
Maximum level dierence (when outdoor unit is lower) 50(40)m
Maximum total piping length in one direction 300m
Outdoor unit
890
(Top plate dimension)
890
(Top plate dimension)
890
(Top plate dimension)
890
(Top plate dimension)
890
(Top plate dimension)
890
(Top plate dimension)
890
(Top plate dimension)
1880
100
200
18 to 32 HP
34 to 48 HP
8 to 16 HP
790
(Installation hole pitch)
790
(Installation hole pitch)
920
(
Installation
hole pitch)
1780
(Installation hole pitch)
950 (Max. dimension)
890
(Top plate dimension)
890
(Top plate dimension)
790
(Installation hole pitch)
920
(
Installation
hole pitch)
950 (Max. dimension)
2870
100
200200
100
790
(Installation hole pitch)
790
(Installation hole pitch)
2770
(Installation hole pitch)
790
(Installation hole pitch)
920
(
Installation
hole pitch)
950 (Max. dimension)
(2 Way version illustrated)
Indoor unit
Indoor unit
HP
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48
Model
C0705DXHN8 C0905DXHN8 C1155DXHN8 C1305DXHN8 C1405DXHN8
10 C0905DXHN8 10 C0905DXHN8 12 C1155DXHN8 14 C1305DXHN8
16 C1405DXHN8 16 C1405DXHN8 16 C1405DXHN816 C1405DXHN8 14 C1305DXHN8 16 C1405DXHN8 16 C1405DXHN816 C1405DXHN8 16 C1405DXHN8 16 C1405DXHN8 16 C1405DXHN816 C1405DXHN8
8 C0705DXHN8
10 C0905DXHN8
10 C0905DXHN8 10 C0905DXHN8
10 C0905DXHN8 12 C1155DXHN8 14 C1305DXHN816 C1405DXHN8 10 C0905DXHN8 10 C0905DXHN8 12 C1155DXHN814 C1305DXHN8 16 C1405DXHN8 16 C1405DXHN8 16 C1405DXHN816 C1405DXHN8
10 C0905DXHN8 10 C0905DXHN8 10 C0905DXHN810 C0905DXHN8 10 C0905DXHN8 12 C1155DXHN8
14 C1305DXHN8
16 C1405DXHN8
Power supply
380/400/415V - 3 phase/50,60Hz
Cooling capacity kW
22.40 28.00 33.50 40.00 45.00 50.40 56.00 61.50 68.00 73.00 78.50 85.00 90.00 96.00 101.00 107.00 113.00 118.00 124.00 130.00 135.00
Heating capacity kW
25.00 31.50 37.50 45.00 50.00 56.50 63.00 69.00 76.50 81.50 87.50 95.00 100.00 108.00 113.00 119.00 127.00 132.00 138.00 145.00 150.00
EER Cooling kW
3.74 3.54 3.50 3.45 3.38 3.63 3.54 3.51 3.49 3.44 3.43 3.41 3.38 3.50 3.47 3.47 3.45 3.42 3.43 3.40 3.38
COP Heating kW
4.05 4.06 3.91 3.91 3.79 4.06 4.06 3.97 3.96 3.88 3.84 3.85 3.79 4.00 3.94 3.89 3.91 3.86 3.83 3.83 3.79
Electric
rating
Cooling
Running
amperes A
10.1/9.6/9.3 13.3/12.7/12.2 16.2/15.4/14.8 20.0/19.0/18.3 23.0/21.8/21.0 23.4/22.3/21.5 26.6/25.4/24.4 29.5/28.1/27 33.3/31.7/30.5 36.3/34.5/33.2 39.2/37.2/35.8 43.0/40.8/39.3 46.0/43.6/42.0 46.6/44.4/42.7 49.6/47.2/45.4 52.5/49.9/48.0 56.3/53.5/51.5 59.3/56.3/54.2 62.2/59.0/56.8 66.0/62.6/60.3 69.0/65.4/63.0
Power
input kW
5.99 7.90 9.58 11.60 13.30 13.90 15.80 17.50 19.50 21.20 22.90 24.90 26.60 27.40 29.10 30.80 32.80 34.50 36.20 38.20 39.90
Heating
Running
amperes A
10.4/9.9/9.5 13.1/12.4/12.0 16.2/15.4/14.8 19.9/18.9/18.2 22.8/21.6/20.9 23.5/22.3/21.5 26.2/24.8/24.0 29.3/27.8/26.8 33.0/31.3/30.2 35.9/34.0/32.9 39.0/37.0/35.7 42.7/40.5/39.1 45.6/43.2/41.8 46.1/43.7/42.2 49.0/46.4/44.9 52.1/49.4/47.7 55.8/52.9/51.1 58.7/55.6/53.8 61.8/58.6/56.6 65.5/62.1/60.0 68.4/64.8/62.7
Power
input kW
6.17 7.75 9.60 11.50 13.20 13.90 15.50 17.70 20.70 22.60 23.10 26.10 28.00 29.30 31.20 30.60 34.70 34.20 37.10 37.90 42.00
Recommended fuse sizes (motor rated)
32 40 32x2 1x40
1x32
1x40
1x32 2x40 2x32
1x40
1x32
2x40 3x40
Dimensions (H/W/D) mm
1887×890×890 (+60) 1887×1880×890 (+60) 1887×1880×890 (+60) 1887×2870×890 (+60)
Net weight kg
245 295 345 540 590 640 640 690 929 985 1035
Air circulation m3/min
150 160 180 200 220 160+150 160+160 180+160 200+160 220+160 220+180 220+220 200+160+160 220+160+160 220+180+160 220+200+160 220+220+160 220+220+180 220+220+200 220+220+220
Piping
connection
Gas
Inches (mm)
3/4 (19.05) 7/8 (22.22) 1 1/8 (28.58) 1 3/8 (34.92) 1 5/8 (41.27)
Liquid
3/8 (9.52) 1/2 (12.7) 5/8 (15.88) 3/4 (19.05)
Balance
1/4 (6.35)
Operating sound normal
mode dB(A)
54.5 55.0 56.0 60.0 61.0 58.0 58.5 61.5 62.0 62.5 63.5 64.0 62.5 63.0 64.5 65.0 65.5 66.0
Operating sound
quiet mode
51.5 52.0 53.0 57.0 58.0 55.0 55.5 58.5 59.0 59.5 60.5 61.0 59.5 60.0 61.5 62.0 62.5 63.0
Ambient temperature
operating range
Cooling
-10°C DB +43°C DB
Heating
-20°C DB +15°C DB
Maximum number of indoor units
13 16 19 23 26 29 33 36 40
* Condenser actual pipe connectio ns may vary from above pip e connections shown , please refer to technic al manuals for full detai ls.
* Please refer to tube sizing charts for pi pe selections and p ipe length paramete rs.