5-3. Insulating the Refrigerant Tubing
Tubing Insulation
●Thermal insulation must be applied to all unit tub- ing, including distribution joint (purchased sepa- rately).
*For gas tubing, the insulation material must be heat resistant to 120°C or above. For other tubing, it must be heat resistant to 80°C or above.
Insulation material thickness must be 10 mm or greater.
If the conditions inside the ceiling exceed DB 30°C and RH 70%, increase the thickness of the gas tubing insulation material by 1 step.
Two tubes arranged together
Narrow tubing | Wide tubing |
Insulation
Three tubes arranged together
Cosmetic
(finishing) tape Wide tubing
Narrow tubing
CAUTION
Taping the flare nuts
If the exterior of the outdoor unit valves has been finished with a square duct covering, make sure you allow suffi- cient space to use the valves and to allow the panels to be attached and removed.
Insulation | Balance tubing | |
|
|
|
|
| Fig. |
Sealer (supplied) |
|
Wind the white insulation tape around the flare nuts at the wide tube connections. Then cover up the tubing connections with the flare insulator, and fill the gap at the union with the supplied black insulation tape. Finally, fasten the insulator at both ends with the sup- plied vinyl clamps. (Fig.
Insulation material
The material used for insulation must have good insu- lation characteristics, be easy to use, be age resis- tant, and must not easily absorb moisture.
After a tube has been insu-
CAUTION lated, never try to bend it into a narrow curve
because it can cause the tube to break or crack.
| Insulation tape (white) | |
| (supplied) | |
| Flare insulator (supplied) | |
Unit side | Tube insulator | |
(not supplied) | ||
insulator | Heat resistant | |
| 120°C or above | |
Flare nut | Vinyl clamps (supplied) | |
| ||
| Fig. | |
| Refrigerant tubing and insulator | |
Drain insulator | (not supplied) | |
Drain pipe and insulator | ||
and clamp. | ||
Large | (not supplied) | |
(supplied) |
| |
Packing |
| |
clamp. | Insulation | |
Small | tape | |
hose band | Vinyl | |
(supplied) | ||
Flare clamp | ||
| ||
| insulator | |
| Seal | |
| The procedure used for | |
| installing the insulator for | |
| both wide and narrow | |
| tubes is the same. |
Fig.
Never grasp the drain or refrigerant connecting outlets when moving the unit.
14