Sanyo SPW-UMR74EXH56, SPW-UMR94EXH56, R410A 5Use shielded wires for inter-unitcontrol wiring

Models: PW-UMR184EXH56 R410A SPW-UMR74EXH56 SPW-UMR224EXH56 SPW-UMR164EXH56 SPW-UMR124EXH56 SPW-UMR94EXH56

1 36
Download 36 pages 7.78 Kb
Page 11
Image 11
(5)Use shielded wires for inter-unit control wiring

(5)Use shielded wires for inter-unit control wiring

(c) and ground the shield on both sides, other- wise misoperation from noise may occur. (Fig. 4-4)

Connect wiring as shown in Section “4-3. Wiring System Diagrams.”

Loose wiring may cause

WARNING the terminal to overheat or result in unit malfunction.

A fire hazard may also exist. Therefore, ensure that all wiring is tightly connected.

When connecting each power wire to the terminal, fol- low the instructions on “How to connect wiring to the terminal” and fasten the wire securely with the fixing screw of the terminal plate.

How to connect wiring to the terminal

For stranded wiring

(1)Cut the wire end with cutting pliers, then strip the insulation to expose the stranded wiring about 10 mm and tightly twist the wire ends. (Fig. 4-5)

(2)Using a Phillips head screwdriver, remove the ter- minal screw(s) on the terminal plate.

(3)Using a ring connector fastener or pliers, securely clamp each stripped wire end with a ring pressure terminal.

(4)Place the ring pressure terminal, and replace and tighten the removed terminal screw using a screw- driver. (Fig. 4-6)

Shielded wire

GroundGround

Fig. 4-4

 

Stranded wire

mm

Ring

10

pressure

Strip

terminal

 

 

Fig. 4-5

 

Special

Screw

 

washer

 

 

Ring pressure

Screw and

 

terminal

 

 

Special washer

Wire

Terminal plate

 

 

Ring

 

 

 

 

pressure

 

 

terminal

 

Wire

 

Fig. 4-6

11

Page 11
Image 11
Sanyo SPW-UMR74EXH56, SPW-UMR94EXH56, SPW-UMR124EXH56, SPW-UMR164EXH56 5Use shielded wires for inter-unitcontrol wiring