3.2BATTERY
The UPS module shall use a valve regulated sealed lead acid
A.Protection Against Deep Discharge and
B.Battery
Battery circuit checks every twelve hours
Partial discharge test every three months
This
4.0OPTIONAL ACCESSORIES
A.Extended Battery Cabinet: Matching battery cabinets shall be furnished in both adjacent or stand alone versions. The cabinet shall match the height and depth of the UPS module and shall have a width of 26”, 36, 48” per battery cabinet. All power wiring and control cables shall be included for adjacent models (remote cabinet cables provided by customer)
B.External Control and Communications Devices
Up to three of the following control and communications devices may be installed in the UPS module:
1.
Requires one communication slot and optional cables. The dry contacts will close on the conditions listed below, but shall be user programmable to close on preset thresholds of other user UPS parameters:
UPS on Line Load on Bypass UPS on Battery Low Battery Warning Battery Fault General Alarm
Two (2) dry contact inputs shall also be provided to turn the UPS inverter on and off remotely upon closure of the contacts. This feature may also be disabled if required.
APC – MGE Galaxy 5000 Specification (60Hz) 11 | Effective: June 1, 2008 REV X0 JJG |