SPECIFICATION KEY
2.2 A–1 OUTPUT POWER RATINGS

40 kVA/ 36 kW

50 kVA/ 45 kW

60 kVA/ 54 kW

80 kVA/ 72 kW

100 kVA/ 90kW

130 kVA /117kW

2.2 A-3 / A-4 INPUT / OUTPUT VOLTAGES

480V Core Voltage Only

2.2 A-5 BATTERY BACK-UP TIME
(minutes)
Configuration Battery 40
kVA 50
kVA 60
kVA 80
kVA 100
kVA 130
kVA
1 x Level 3 NPX-150 11 9 x x X X
1 x Level 4 300 WPC 28 22 16 10 x x
1 x Level 5 400 WPC 41 31 24 16 11 7
1 x Level 6 500 WPC 59 46 36 25 17 11
2 x Level 5 400 WPC 90 72 57 41 31 22
2 x Level 6 500 WPC X x 81 58 47 33
3 x Level 6 500 WPC X x 127 94 71 54
Additional configuration and runtimes are available.
2.2 B-2 INPUT CURRENTS
40 KVA 50 KVA 60 KVA 80 KVA 100
KVA 130
KVA
A @ 480 VAC
Max – Charging Battery
59 70 88 111 150 182
2.2 B-2 OUTPUT CURRENTS
40 KVA 50 KVA 60 KVA 80 KVA 100
KVA 130
KVA
A @ 480 VAC 48 60 72 96 120 156

APC – MGE Galaxy 5000 Specification (60Hz) 15 Effective: June 1, 2008 REV X0 JJG
Parallel Module