SPECIFICATION KEY
2.2
OUTPUT POWER RATINGS
40 kVA/ 36 kW
50 kVA/ 45 kW
60 kVA/ 54 kW
80 kVA/ 72 kW
100 kVA/ 90kW
130 kVA /117kW
2.2
480V Core Voltage Only
2.2A-5 BATTERY BACK-UP TIME
|
|
| (minutes) |
|
|
| |
Configuration | Battery | 40 | 50 | 60 | 80 | 100 | 130 |
|
| kVA | kVA | kVA | kVA | kVA | kVA |
1 x Level 3 | 11 | 9 | x | x | X | X | |
1 x Level 4 | 300 WPC | 28 | 22 | 16 | 10 | x | x |
1 x Level 5 | 400 WPC | 41 | 31 | 24 | 16 | 11 | 7 |
1 x Level 6 | 500 WPC | 59 | 46 | 36 | 25 | 17 | 11 |
2 x Level 5 | 400 WPC | 90 | 72 | 57 | 41 | 31 | 22 |
2 x Level 6 | 500 WPC | X | x | 81 | 58 | 47 | 33 |
3 x Level 6 | 500 WPC | X | x | 127 | 94 | 71 | 54 |
| Additional configuration and runtimes are available. |
|
|
|
| ||
2.2 | INPUT CURRENTS |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 40 KVA | 50 KVA | 60 KVA | 80 KVA | 100 | 130 |
|
|
|
|
|
| KVA | KVA |
| A @ 480 VAC | 59 | 70 | 88 | 111 | 150 | 182 |
| Max – Charging Battery |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2.2 | OUTPUT CURRENTS |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 40 KVA | 50 KVA | 60 KVA | 80 KVA | 100 | 130 |
|
|
|
|
|
| KVA | KVA |
| A @ 480 VAC | 48 | 60 | 72 | 96 | 120 | 156 |
|
|
|
|
|
|
|
|
APC – MGE Galaxy 5000 Specification (60Hz) 15 | Effective: June 1, 2008 REV X0 JJG |
Parallel Module |
|