Smart-UPS X-Series Operation10
Network Management Card Settings

These settings are available only on units that have a Network Management Card (NMC) and are set in

the factory. These settings can only be modified using an external interface, like the NMC web interface.

• NMC IP Address Mode

• NMC IP Address

NMC Subnet Mask

NMC Default Gateway

Load Shed Time
when On Battery Disabled 0-32767 sec The amount of time the outlets will function on
battery power before they will turn off.
Load Shed On
Runtime Disabled Shutdown with
delay
Shutdown
immediately
•Turn off
immediately
•Turn off with
delay
• Disabled
When the battery runtime falls below the
specified value, the Controllable Outlet Group
will turn off.
Configure this time using the LOAD SHED
RUNTIME REMAINING setting.
Load Shed On
Runtime
Remaining
Disabled 0-32767 sec When the remaining runtime reaches this level,
the Controllable Outlet Group will turn off.
Load Shed on
Overload Disabled •Disabled
•Enabled (Applicable only for Controllable Outlet
Groups, not the UPS outlets.) When enabled,
the Controllable Outlet Group will turn off
immediately in the event of a power outage
and will have to be manually restarted.
Function Factory Default Options Description