Smart-UPS X-Series Operation2
Specifications

Operating Conditions

This unit is intended for indoor use only. Select a lo cation s turdy enoug h to support the weight of the uni t
and External Battery Packs (XLBP).
Do not operate the UPS where there is excessive dust, or the temperature or humidity are outside the
specified limits.
This unit has front and rear air vents. Allow adequate space for proper ventilation.

Environmental Specifications

Environmental factors impact battery life. High temperatures, poor utility power, and frequent, short
duration discharges will shorten battery life.
For additional specifications, see the APC Web site at www.apc.com.
Installation

UPS

For UPS installation information, see the Smart-UPS X-Series Quick-Start guide that is
included with the UPS. The guide is also available on the enclosed CD and the APC Web sit e
at www.apc.com.

Network Management Card

For installation information, see the user manual provided with the Network Management
Card (NMC). The user manual is also available on the APC Web site at www.apc.com.

External Battery Pack

For installation information, see the Smart-UPS X-Series External Battery Pack Installation
guide that is included with the external battery pack. The guide is also available on the
enclosed CD and the APC Web site at www.apc.com.
Temp era tur e Operating 0° to 40° C (32° to 104° F)
Storage -15° to 45° C (5° to 113° F)
charge UPS battery every six months
Maximum
Elevation Operating 3,000 m (10,000 ft)
Storage 15,000 m (50,000 ft)
Humidity 0% to 95% relative humidity, non-condensing