Schneider Electric C3419M-D (11/08) manual Ac/Dc, Wire Gauge, Total VA, Receiver

Models: C3419M-D (11/08)

1 16
Download 16 pages 28.89 Kb
Page 3
Image 3

1.Locate the center point of the mounting location and insert the compass tool into the ceiling. Draw a circle.

2.Cut out the circle.

3.Use the mounting ring as a template to mark the screw hole pattern onto the mounting surface. Prepare the holes.

4.Install the mounting plates. Use the eight 10-32 x 3-inch screws (supplied) to install the mounting ring (A) and the two back mounting plates (B).

a.Line up the mounting ring with the eight fastener holes.

b.Feed one back mounting plate (B) through the hole in the ceiling (C). Line up the plate with the four fastener holes.

c.Install fasteners through the mounting ring (A), ceiling, and out the back mounting plate (B).

d.Install the second back mounting plate (B).

5.Attach a conduit fitting (not supplied), lock nut (not supplied), and safety chain bracket. Install a safety chain/cable (not supplied), which will support up to 16 pounds (7.3 kg).

6.Open the hinged door to the back box. Push the tab lock toward the wall of the unit and lift the door open. Pull the wiring into the back box through the conduit fitting. Refer to Table A, Table B, and Table C for wiring distances.

Table A. Video Coaxial Cable Requirements

Cable Type*

Maximum Distance

 

 

RG59/U

750 ft (229 m)

 

 

RG6/U

1,000 ft (305 m)

 

 

RG11/U

1,500 ft (457 m)

 

 

*Cable requirements: 75-ohm impedance All-copper center conductor

All-copper braided shield with 95% braid coverage

Table B. 24 VAC/24VDC Wiring Distances

Below are the recommended maximum distances for 24 VAC and 24 VDC applications and are calculated with a 10 percent voltage drop. (Ten percent is generally the maximum allowable voltage drop for AC- or DC-powered devices.)

AC/DC

 

Wire Gauge

 

Total VA/

20 AWG

18 AWG

16 AWG

14 AWG

Total Watts

(0.5 mm2)

(1.0 mm2)

(1.5 mm2)

(2.5 mm2)

23 VA/

123 ft

196 ft

311 ft

495 ft

15 W

(38 m)

(60 m)

(95 m)

(151 m)

 

 

 

 

 

NOTE: Input power for the dome is 24 VAC or 24 VDC. Using 24 VAC input power, power consumption is 23 VA per dome. Using 24 VDC input power, power consumption is 0.7 A (15 W). Use a 24 VAC transformer with a minimum of 40 VA per dome.

.

Table C. UTP Wiring Distances

Receiver

Maximum Distance

 

 

Active

0-3,000 ft

(Video Only)

(0-914.4 m)

 

 

Passive

0-750 ft

(Video, Coaxitron®, Pelco V-Sync)

(0-228.6 m)

NOTE: As a minimum, UTP requires Cat5, 100-ohm twisted pair cable.

C3419M-D (11/08)

3

Page 3
Image 3
Schneider Electric C3419M-D (11/08) manual Ac/Dc, Wire Gauge, Total VA, Receiver