Sea-Fire FM200 manual Area, Diameter Model, Auto, Lbs, Part#

Models: FM200

1 14
Download 14 pages 1.65 Kb
Page 2
Image 2

WARNING

CONCENTRATED AGENT AND BY-PRODUCT OF APPLICATION TO FIRE ARE TOXIC. AVOID BREATHING OF FUMES OR PROLONGED EXPOSURE. ACCIDENTAL DIS- CHARGE MAY OCCUR DURING HANDLING OR INSTALLATION OF THIS DEVICE, READ AND COMPLY WITH INSTRUCTIONS, WARNINGS, AND LIMITATIONS CONTAINED IN THIS MANUAL. DO NOT LIFT, CARRY, OR HANDLE BY VALVE. DO NOT DROP. KEEP AWAY FROM HEAT. KEEP AWAY FROM CHILDREN.

APPLICATION

FM-200®(CF3CHFCF3), the extinguishing agent, used in all Sea-Fire “FT’’ series fire extin- guishers, is a suitable EPA accepted alternate replacement for Halon. FM-200®is electrically nonconductive and residue free extinguishing agent that requires no cleanup.

These features and the versatility of design make the “FT’’ series fire extinguisher ideal for a broad range of applications. The systems are ideal for small volumes, 150 cubic feet or less, that are difficult to access. These applications would include marine, recreational vehicles, commercial and industrial use where flammable liquids are likely source of fire.

Application Examples:

Engine Compartments (maximum 150 cubic feet)

Bow Thrusters

Small Generator Set Enclosures

Consoles

Electrical Enclosures

Flammable Liquid Storage Areas

Pump Enclosures

Alternative Fuel Storage Areas

Sea-Fire “FT” extinguishers are designed to induce a minimum atmospheric concentration of 10.0% within the protected compartment.* The specification table in this manual lists the minimum and maximum approved compartment volume (size) allowable for each model. Volume can be determined by multiplying the compartment’s length x width x height which equals the volume in cubic feet or meters (LxWxH=V).

Exception: If the boat manufacturer has placed a permanently affixed label in the compart- ment specifying the gross volume less the volume of permanently installed tankage, then this volume may be used to determine the proper size extinguisher. Check specification table for proper application before making installation.

*Reference: NFPA-2001 National Fire Protection Assoc. Boston, MA and UL 2166 Underwriters laboratories

SEA-FIRE “FT” SERIES AUTOMATIC FIRE SUPPRESSION SYSTEMS FT — STINGER SPECIFICATION TABLE

 

AREA OF

FM-200 @

 

DIAMETER X

 

 

 

 

MODEL

PROTECTION

240 PSI

 

HEIGHT

TUBE PART # / LENGTH

 

CU.FT.

CU.M.

 

 

 

 

 

 

 

 

 

AUTO

AREA

AREA

LBS.

KG

 

INCH

MM

PART#

 

FT.

MM

FT-25

25

0.7

1.25

0.56

 

3.0 X 11.2

76 X 285

130-121

 

10

3000

FT-50

50

1.4

2.50

1.13

 

3.1 X 13.5

78 X 342

130-121

 

10

3000

FT-75

75

2.1

3.75

1.70

 

3.1 X 16.5

78 X 419

130-121

 

10

3000

FT-100

100

2.8

5.00

2.26

 

3.5 X 17.5

89 X 444

130-122

 

15

4500

FT-125

125

3.5

6.25

2.83

 

4.1 X 17.0

104 X 432

130-122

 

15

4500

FT-150

150

4.2

7.50

3.40

 

5.2 X 19.0

132 X 482

130-122

 

15

4500

 

 

 

 

 

 

 

 

 

 

 

 

CU. FT. = Cubic Feet

 

 

FT. = Feet

 

 

KG = Kilograms

CU.M. = Cubic Meters

 

 

LBS. = Pounds

 

MM = Millimeters

CAUTION: NEVER INSTALL A UNIT WITH A VOLUME RATING LESS THAN THE GROSS VOLUME OF THE COMPARTMENT TO BE PROTECTED. DO NOT DEDUCT FOR ENGINES, REMOVABLE TANKS OR OTHER EQUIPMENT.

2

Page 2
Image 2
Sea-Fire FM200 manual Area, Diameter Model, Auto, Lbs, Part#

FM200 specifications

Sea-Fire FM200 is an advanced fire suppression system specifically designed for marine environments and critical asset protection. This highly-effective system utilizes hydrofluorocarbon (HFC-227ea) as its primary extinguishing agent, which is known for its excellent firefighting properties. The FM200 system is particularly favored for its ability to put out fires without causing damage to sensitive electronic equipment, making it an ideal choice for vessels, offshore platforms, and industrial facilities.

One of the main features of Sea-Fire FM200 is its rapid-fire extinguishing capability. The gas can suppress flames in just ten seconds, significantly minimizing damage and ensuring safety. This quick-response characteristic is critical in marine environments where fires can spread rapidly and pose severe risks to life and property.

The Sea-Fire FM200 system is designed with a flexible configuration, allowing it to be tailored to fit various vessel designs. This adaptability includes options for multiple storage containers and different discharge nozzles, ensuring comprehensive coverage of the protected area. This flexibility is crucial for accommodating the varying layouts found on ships, allowing for optimal placement of the system's components.

Another notable feature is the system’s automatic activation capability. Integrated with the latest detection technologies, Sea-Fire FM200 employs advanced smoke and heat detectors that can autonomously trigger the suppression system in the event of a fire. This automated functionality enhances safety by providing immediate response even in situations where personnel may not be present.

The Sea-Fire FM200 system also emphasizes ease of maintenance and reliability. Regular checks and servicing can be done without extensive downtime, allowing vessels to maintain operational efficiency. The system's components are designed to withstand harsh marine conditions, ensuring long-lasting performance.

In terms of environmental considerations, FM200 is often chosen for its low ozone depletion potential compared to other agents. It consists of a clean agent that won’t leave residues, making post-fire clean-up easier and minimizing the impact on marine ecosystems.

In summary, Sea-Fire FM200 stands out as a superior fire suppression solution in the maritime industry. With rapid extinguishing capabilities, flexibility for various installations, automatic activation through advanced detection systems, low environmental impact, and durability, it serves as a critical component in safeguarding vessels and valuable assets from the devastating effects of fire.