IGWiPS200-1

PULSE OUTPUT MODULE DIAGNOSTIC LED’S

There are 3 diagnostic LED’s on the pulse output module:
Status LED: On solid when I/O is functional and flashing if there is a conflict with another module.
Pulse Input 1 and 2 LEDs: These lights will flicker at a varying frequency depending on the frequency of
pulses being generated:
Frequency Range (Hz) LED Flashing Frequency (Hz)
1 frequency 10 1
10 < frequency 100 4
100 < frequency 1000 8
1000 < frequency 32K On solid
SPECIFICATIONS
Transceiver
Frequency.............................................................902 to 928 MHz industrial, scientific, and medical (ISM) band
Technology...........................................................Frequency Hopping Spread Spectrum
Power Input.......................................................... 9-30 Vdc; reverse polarity and surge protected
Power Consumption.............................................75 mA (average), 200 mA (peak) @ 24 Vdc during transmission
(plus I/O modules), 5A (maximum)
Inputs
Analog...........................................................1, 4 to 20 mA (16-bit, 125 Ohms impedance
Digital............................................................2, 5 to 36 Vac/Vdc (for 120 Vac digital inputs use relays to convert
to specified voltage levels; consult factory for relay options)
Outputs
Analog...........................................................1, 4 to 20 mA, 12-bit resolution, short circuit protected
Digital............................................................2, 250 Vac / 30 Vdc, 2A dry contact
RF Link.........................................................1, 250 Vac / 30 Vdc, 2A dry contact
Repeatability (4-20 mA Current Loop)................0.02%
Accuracy (4-20 mA Current Loop)......................0.2% full scale
Transmitter Power Output....................................1 Watt (30 dBm)
Range
Standard Omnidirectional Antenna...............600 to 1000 feet (183m to 305m) in-plant, obstructed LOS6
Optional Omnidirectional Antenna...............4 to 5 miles (6.5 km to 8 km) clear LOS, flat terrain, raised antenna
Optional Yagi Antenna..................................15 to 20 miles (24 km to 32 km) clear LOS, flat terrain,
professional propagation study and installation
Antenna Connector...............................................MCX female, 50 Ohms
Operating Temperature Range..............................-40°C to 70°C (-40°F to 158°F)
Humidity...............................................................20% to 90% non-condensing
Dimensions...........................................................4.5" x 3.9" x 0.9" (114 mm x 99 mm x23 mm)
Faceplate Label Color...........................................White
Weight..................................................................5.3 oz (150g)
Environmental......................................................NEMA 1, equivalent to IP 20
Approvals
USA...............................................................FCC 47CFR15.247
Canada...........................................................ISC RSS 210
UL and CUL..................................................Class I, Div. 2, Groups A, B, C, D; Temp. Code T5
CSA...............................................................Approved
6 LOS – Line of Sight between transmitting and receiving antennas
May 2007 31