4PC/TS Adapter
A5E00078070-02
2 Package Components
SAdapter
SQuick Reference Guide
SMounting assembly (TS adapter only)
3 Accessories (not part of the adapter package)
SRS232 cable, 6 meters in length 6ES7 901-1BF00-0XA0
(required to operate the PC adapter and to operate the
TS adapter in direct connection only).
4 MPI/DP Network
A maximum of 32 nodes can be interfaced to an MPI/DP
network segment. The total cable length may not exceed 50
meters. Using so-called RS485 repeaters, several network
segments can be combined to form a network comprising a
maximum of 127 nodes.
The data signalling rate in an MPI/DP network is max. 12
Mbit/s.
Der Adapter unterstützt Übertragungsraten bis max.
1,5 Mbit/ s.
Note
Also refer to “S7-300, Hardware and Installation”.
!Warning
If the transmission rate is 187.5 Kbits/sec and
higher, it is not allowed to insert cable extensions
in the S7/M7/C7 adapter system connection