VCAUTION
CONDUCTING DIELECTRIC AND/OR
Do not perform dielectric or high potential
tests with the TPS3 unit installed.
V DANGER
Hazardous voltage.
Will cause death or serious injury.
Keep Out.
Qualified personnel only.
Disconnect and lock off all power before working on this equipment.
Maintenance | Warranty and Customer Service |
SPDs require minimal maintenance. Periodic inspection of diagnostic indicators is recommended to ensure proper operation.
Troubleshooting & Service
Please contact us for any service related issues.
Quality SPDs withstand severe duty and attempt to protect their load until failure. There are electrical anomalies that SPDs cannot protect against. These are generally Sustained Overvoltages also known as Temporary Overvoltages (TOVs). In this context, Sustained Overvoltages may be only a few cycles. Failed SPDs tend to be symptoms, not root causes. A failed SPD is usually a sign of other problems within the electrical distribution system. As a generalization, the single largest cause of SPD failures is reference to ground issues. If the SPD shows problems on startup, there is reasonable chance of bonding/grounding/misapplication issue. This permanently damages the unit. If not corrected, it will happen again.
Limited Warranty
Siemens warrants its AC Panel protection products against defective workmanship and materials for 10 years. Liability is limited to the repair or replacement of the defective product at Siemens’ option. A Return Material Authorization number (RA#) must be given by the company prior to the return of any product. Returned products must be sent to the factory with the transportation charges prepaid. In addition, the company also warranties unlimited replacement of modular and component parts within the warranty period previously described.
The company specifically disclaims all other warranties, expressed or implied. Additionally, the company is not be responsible for incidental or consequential damages resulting from any defect in any product or component thereof.
The sales contract contains the entire obligation of Siemens. This instruction manual shall not become part of or modify any prior existing agreement, commitment or relationship.
Technical Support
1.888.333.3545
Prior to calling Siemens TPS3 Technical Support for assistance or ordering parts, please have the following information available:
TPS3 model number: ________________________________
Manufacture date: _________________________________
Date of Purchase: ___________________________________
Your order number: _______________________________
Return Shipment Address:
Siemens - Attn: RA #___________
14550 58th Street North
Clearwater, FL 33760
10