Floor Protection
All woodstoves require floor protection when installed on a com bustible surface. You must place use protector equivalent to 3/8' asbestos millboard covered with 24 gauge metal. The floor protector must extend 16" in front of the door side, 8" on each side and 8" in the rear of the unit and under the chim ney connection and 2" beyond each side. See Figure 4.
The k, C or R factor that correlates with the floor protector m aterial used during the test if the room heater is not provided with a floor protector. The units of measure for k, C and R factors shall use the sam e applicable units. Directions and exam ples on how to use alternate materials and how to calculate equivalent thickness shall be shown.
An easy means of determ ining if a proposed alternate floor protector meets requirem ents listed in the appliance
m anual is to follow this procedure:
1.Convent specifications to
a.
b.
c.
2.Determ ine the
a.Use the form ula in step 1 to convert values not expressed as “R”.
b.For m ultiple layers, add
3.If the overall
EXAMPLE:
The specified floor protector should be 3/4 inch thick m aterial with a
The proposed alternate is 4" brick with a
Step 1: Use form ula above to convert specification to
Step 2: Calculate R of proposed system . 4" brick of C - 1.25, therefore
R brick = 1/C = 1/1.25 = 0.80
1/8" mineral board of k+ 0.29, therefore R m in.bd. = 1/0.29 x 0.125 = 0.431
Total R = R brick + R brick + R mineral Board = 0.8 + 0.431 = 1.231
Step 3: Com pare the proposed system R of 1.231 to specified R of 0.893. Since proposed system
R is greater than required, this is acceptable. Definitions:
Note: Asbestos cannot be used. Asbestos is used as a standard only. 3/8 inch asbestos millboard has a “K” factor of 0.84. The newer substitute CERAFORM board has a “K” factor of 0.21. Your floor protector must have an equivalent or better “K” factor than the above recomm endations.
10