Sierra Monitor Corporation dimensions Specifications, Additional Features, Model 3200 Series

Models: 3200 Series

1 2
Download 2 pages 10.88 Kb
Page 2
Image 2
Model 3200 Series

Model 3200 Series

Flame Detectors

Specifications

 

Sensitivity:

3.0 seconds to a 4 inch diameter

 

isopropyl alcohol pan fire (on-axis)

 

@ 10 feet

Field of View:

120o full cone

False Alarm

Does not alarm to sunlight,

Immunity:

fluorescent lights, flashlights, or

 

infrared heaters.

Input Voltage:

12 to 30 volts DC typically 24 VDC

Current Draw:

@24 VDC; 28 mA normal mode; 54 mA

 

alarm mode

Operating Range

Operating: 32o to 167oF (0o to 75o C)

Temperature:

 

Storage: -40oto 185o F ( -40oto 85o C)

Humidity:

10 to 90% RH

Typical Fire Type:

FR & HB polypropylene and

 

isopropyl alcohol

Red LEDs:

Two, indicating Normal

 

Operation and Trouble/Alarm

Alarm Relay:

1.0 amp @ 30 VDC resistive

Trouble Relay:

1.0 amp @ 30 VDC resistive

UV Sensor:

Solar-blind Ultraviolet sensor - radiant

 

energy in the 185 to 260 nm band

IR Sensor:

Solid state infrared sensor detecting -

 

IR energy in the .715 to 3.5 microns

Acid/Solvent

Resistant to sulfuric acid,

Resistant Surfaces:

phosphoric acid, hydrofluoric acid,

 

hydrochloric acid, ammonium

 

hydroxide, nitric acid, isopropyl

 

alcohol, deionized water, chromium

 

phosphate, n-methyl-pyrrolidane,

 

organic solvent base photoresist

 

strips, ozone, etc.

Housing:

FR Polypropylene (IP67, UL94

 

flamability rating V0) or

 

(Polyvinylidene Fluoride - PVDF

 

available) (for models -2X and -3X)

 

with a 6 foot pigtail (8 wires

 

standard - 4 wires for the fire relay, 2

 

wires for the trouble relay and 2

 

wires fro the power)

Dimensions:

3.4 x 4.2 x 1.0 inches

 

(8.6 x 10.7 x 2.5 cm)

Weight:

1 lb (0.5 Kg)

Approval:

FM Approved, CSFM 7210-1608:101

Additional Features

Self-Test Models:

Incorporate internal self-test for UV

 

lamp

Enhanced Models:

Incorporate internal self-test and a

 

RS-485 computer interface for

 

downloading real time spectral data

 

pre-fire spectral data (includes 2

 

additional wires in pigtail)

False Alarm and Fire Response

"This table shows the detectors ability to tolerate both modulated and unmodulated false alarm stimuli and still

to detect a fire in the presence of the false alarm source (all fire tests used a 1.75" diameter alcohol pan fire at

6 feet)

 

 

 

 

 

False Alarms Source

Distance

Unmodulated

Modulated

Response Time to Fire

 

 

 

 

 

Resistive Electric Heater 1320 Watt

6 Feet

No Response

No Response

Less than 3 sec.

 

 

 

 

 

Fluorescent Lights (2) 40 Watt Bulbs

6 Feet

No Response

No Response

Less than 3 sec.

 

 

 

 

 

Halogen Light 500 Watt

10 Feet

No Response

No Response

Less than 3 sec.

 

 

 

 

 

Incandescent Light 100 Watt

6 Feet

No Response

No Response

Less than 3 sec.

 

 

 

 

 

 

 

 

 

 

 

 

Ordering Information

 

 

 

 

 

 

 

 

 

 

3200-01

Standard, (Normally Closed - NC Trouble Relay)

 

 

 

 

 

 

 

 

3200-02

Self-test, (NC Trouble Relay)

 

 

 

 

 

 

 

 

 

 

3200-03

Enhanced, (NC Trouble Relay)

 

 

 

 

 

 

 

 

 

3200-04

Standard, with SealCon and Turk connectors (NC Fire, NC

 

 

Trouble)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Options:

 

 

 

 

 

 

 

 

 

 

 

3240-01

Flame Detector Tester (for Model 3200 Flame Detector)

 

 

 

 

 

 

 

 

Sierra Monitor Corp 1991 Tarob Court Milpitas, CA 95035 USA (408) 262-6611 (800) 727-4377 Fax: (408) 262-9042

Visit our Web site: www.sierramonitor.com

E-Mail: sierra@sierramonitor.com

© 2009 by Sierra Monitor Corporation Rev. B2-02-23-09