Sentry Printer Option
The Sentry Printer Option aids in management of your gas risk with the ability to print a variety of complete reports.
Sentry's preformatted reports provide critical information for analyzing gas exposure and evaluating system reliabil- ity. Report selection criteria are user definable. These reports:
•Help user make better decisions during a gas leak
•Provide history to analyze all exposure events
•Substantiate due diligence in complying with regu- lations
•Confirm the reliability of the system.
With optional Sentry printer software, preformatted reports can be printed via the RS232 port on the Sentry connector panel. Output is either directly from one controller to a printer or, via the Sentry Master and Subordinate network system, from several controllers to one printer.
STATUS REPORT
Status Reports show a snapshot of the gas concen- tration and alarms. The reporting interval is user pro- grammable from 1 hour to 7 days. The first line indi- cates the controller ID and date/time. The second line indicates the sensor number and alarm condition (“L” for low alarm and “H” for high alarm). The third line indicates the current concentration and the fourth line indicates the gas type.
| |||||||
|
| <STATUS | REPORT> |
|
| ||
ID:A STATUS = | 01 HOUR 12/17 15:00 |
| |||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 |
03 | 04 | 20.9 | 20.9 | 08 | 08 | 18 | 19 |
H2S COMB OXY | OXY | COMB COMB COMB COMB | |||||
| |||||||
|
| <STATUS | REPORT> |
|
| ||
ID:A STATUS = | 01 HOUR 12/17 16:00 |
| |||||
1L | 2 | 3 | 4 | 5 | 6 | 7 | 8 |
03 | 04 | 20.9 | 20.9 | 08 | 09 | 08 | 08 |
H2S COMB OXY | OXY | COMB COMB COMB COMB | |||||
| |||||||
|
| <STATUS | REPORT> |
|
| ||
ID:A STATUS = | 01 HOUR 12/17 17:00 |
| |||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 |
13 | 04 | 20.9 | 20.9 | 08 | 09 | 22 | 19 |
H2S COMB OXY | OXY | COMB COMB COMB COMB |
<STATUS | REPORT> |
|
|
|
| ||
ID:A STATUS = 01 | HOUR 12/17 18:00 |
| |||||
1H | 2 | 3L | 4 | 5 | 6 | 7L | 8 |
23 | 04 | 19.5 | 20.9 08 | 06 | 40 | 19 | |
H2S | COMB OXY | OXY COMB COMB COMB COMB |
Printer (5301-10)
The Sentry Printer is a modern,
This printer utilizes thermal paper and thus no ink! It has minimal moving parts, easy maintenance with
10 is
Serial/Parallel Compact Printer | |
SPL69207 | 120V Power Supply |
SPL69205 | Thermal Paper for Compact Printer |
SYSTEM REPORT
The System Report lists all the system parameters including the software configuration of the system, cali- bration configuration, printer configuration and configu- ration for each module: on/off condition, calibration sta- tus, relay latching configuration, alarm levels, module type, the controller channel to which it is connected, and calibration conditions and factors.
<SYSTEM REPORT> |
|
| ||
ID:A | USER # = 1 12/17 | 15:08 | ||
M5000 | VER:4.19 |
|
| |
PN 8C |
|
|
|
|
CALIBRATION CONFIGURATION: |
| |||
LC: OFF | CAL FREQ= | 90 | DAYS | |
H2S = 20 | CAL DUE = | 88 | DAYS | |
COMB= 60 | CAL DUE = | 89 | DAYS <SEL> | |
PRINTER CONFIGURATION: |
| |||
PRINTER: ON | STATUS = | 07 DAYS HIST:YES | ||
H2S : MIN. CONC. = 05 | CHANGE = 03 | |||
COMB: MIN. CONC. = 08 | CHANGE = 13 |
MODULE CONFIGURATION : |
| |||||
MODULE | 1 | IS ON | H2S | CHANNEL=1 | ||
LA= 10 NLATCH | HA= | 20 | LATCH | |||
FACTOR(S)= | 100 | 150 | 200 | |||
MODULE | 2 | IS | ON | COMB CHANNEL 2 |
DIAGNOSTIC REPORT
The Diagnostic Report lists the critical voltage conditions for each module and can be selected to print periodically at intervals from 1 to 90 minutes.
Sierra Monitor Corp. 1991 Tarob Ct., Milpitas, CA 95035, USA,
Web Site: http://www.sierramonitor.com |