Simpson Electric H340 Frequently Asked Questions, Power Supply Card, Output Control If Present

Models: H340

1 12
Download 12 pages 30.94 Kb
Page 11
Image 11

The relay cards are directly related to any alarms that occur on the Hawk 3. The single relay is a “Form C” relay that activates in relationship to “SP1”. The dual relay is a Form C” relay that activates in relationship to “SP1” & “SP2”.

The quad relay is a “Form A” relay that activates in relationship to “SP1” through “SP4”.

NOTE: “SP3” and “SP4” connections share a common.

!

All relay contacts are rated at 250VAC @ 5 amp maximum. The rating of the relay contact is intended for resistive circuits only. Use a snubber circuit to protect the contacts from inductive loads.

7.2Frequently Asked Questions

What is a Form A or Form C relay?

The form A relay is a 1 contact switch that is either closed or open. The form C relay has 2 contacts, one of which will be closed and one open. With the fac- tory defaults used, N.O. on the relay means normally open when the Hawk 3 is not in alarm. N.C. means normally closed when the Hawk 3 is not in alarm.

What does N.D. and N.E. do to the relay?

The effect of the relay can be reversed by setting the relay action to N.E. (nor- mally energized) in the menu. When the Hawk 3 is not in alarm, the N.C. contact will now be open and the N.O contact will be closed. Setting the alarm response back to N.D. (normally de-energized) will put the contacts back to their default state.

7.3Power Supply Card

Universal AC Supply 3-1/2 Digit 120 VAC Supply DC to DC Supply

6.4

Output Control (If Present)

 

 

 

 

 

 

 

 

 

 

OctL

 

 

 

 

 

ALog out

 

 

 

 

 

 

LIM

HI (electrical limit)

 

 

 

 

 

(100*)

 

 

 

 

 

Lo (electrical limit)

 

 

 

 

 

(0*)

 

 

 

 

FS (Fail safe)

HI (move to 20mA)

 

 

 

 

(Overrange or Underrange

LO (move to 4mA)

 

 

 

 

 

Off*

 

6.5System Control

(The process meter will have pre-loaded coordinates)

SctL

 

FACT/rSET (Factory

Reset (Selecting this item will reset the

 

Reset)

device to default values and return to

 

 

menu)

IN ~

IN

~

IN ~

IN

~

85-250VAC

85 - 250 VAC

50/60 Hz

50/60 Hz

10VA

10VA

HOLD

HOLD

+

9-36VDC

10W

HOLD

The AC power cards are meant to operate from standard 50/60 Hz line power. The DC to DC power card is an isolated supply that can operate between 9 and 32 volts DC.

14

11

Page 11
Image 11
Simpson Electric H340 manual Frequently Asked Questions, Power Supply Card, Output Control If Present, System Control