Smeg A11A-6 manual Instructions for the installer, Room ventilation, Requirements

Models: A11A-6

1 32
Download 32 pages 9.76 Kb
Page 6
Image 6
2.3 Room ventilation

Instructions for the installer

2.3 Room ventilation

Caution – This cooker may only be installed and operated in rooms permanently ventilated in accordance with current regulations. For proper operation of a gas appliance it is essential for the air necessary for combustion of the gas to be able to flow naturally into the room. Air must flow directly into the room through openings in its outside walls. This (these) opening (s) must have a free passage cross-section of at least 100 cm2, or 200 cm2 for appliances not equipped with gas safety device. These openings must be constructed so that they cannot be obstructed indoors or outdoors, and should preferably be close to the floor on the side opposite to the combustion gas discharge point. If it is not possible to make the openings in the room where the cooker is installed, the necessary air may be taken from an adjoining room, proveded it is not a bedroom or a room with fire risk.

2.4Clearance above and around domestic cookers

Extract from AS5601

REQUIREMENTS

8

Page 6
Image 6
Smeg A11A-6 Instructions for the installer, Room ventilation, Clearance above and around domestic cookers, Requirements