SPX Cooling Technologies 92-1322C user manual Operation, Method B

Models: 92-1322C

1 16
Download 16 pages 30.4 Kb
Page 10
Image 10

/ Operation /

Method B

1.Disconnect power to the heater control panel using standard lockout procedures for safety.

2.Drain basin until the water level is below the probe allowing removal of the probe. Make sure water still covers the heater elements.

3.Place the probe in a container of ice water making sure both metal parts of the probe are submerged but not the cord.

4.Energize the heater control panel. Allow 5 min. for the probe tempera- ture to stabilize.

5.An audible CLICK should be heard as the heater contactor engages. If this does not happen, refer to the Troubleshooting section.

10

Page 10
Image 10
SPX Cooling Technologies 92-1322C user manual Operation, Method B