/ Troubleshooting /

2.If the contactor does not operate, check voltage across terminal N on the circuit board and NO on the relay mounted on the circuit board —21-29 volt required. If voltage is present across the coil—N to NO— the contactor coil is defective and the contactor must be replaced. If voltage is not present, the circuit board relay is defective and the circuit board must be replaced.

C. If the green LED is off and the red LED is also off the problem is either the circuit board, the sensor probe, or the transformer. To determine which check as follows:

1.Disconnect power and remove wires T1 and T2 from the circuit board. Replace with the 1.5K ohm resistor provided. See Figure 2. If the system now works, the sensor probe is defective and must be replaced. If the system does not work, go to step 2.

2.Reconnect power and take a voltage reading across N and 24/240 on the circuit board—21-29 volts required. If proper voltage is not present the transformer is defective and must be replaced. If proper voltage is present go to step 3.

3.Take a voltage reading across N and NO—21-29 volts required. If proper voltage is not present, replace circuit board.

6.The sensor assembly can be checked for accuracy in the following manner.

Remove wires T1 and T2 from the circuit board and measure ohm readings across these wires. Measure the water temperature that the probe is being exposed to. Compare with the following values.

Table 4

Temp °F

ohms

 

0

4273

 

 

 

 

10

3126

 

 

 

 

20

2312

 

 

 

 

32

1633

 

 

 

 

40

1305

 

 

 

 

45

1138

 

 

 

 

60

765

 

 

 

 

75

525

 

 

 

 

85

412

 

 

 

13

Page 13
Image 13
SPX Cooling Technologies 92-1322C user manual Temp F Ohms

92-1322C specifications

SPX Cooling Technologies 92-1322C is a state-of-the-art cooling tower designed to meet the demands of various industrial applications. Known for its robust construction and advanced engineering, this unit offers exceptional performance while maintaining energy efficiency.

One of the main features of the 92-1322C is its durable structure. The cooling tower is built with high-quality materials that resist corrosion and withstand harsh environmental conditions. The fiberglass-reinforced plastic casing ensures longevity and minimizes maintenance costs over time. In addition, the unit is equipped with a galvanized steel support frame that provides stability and strength.

The 92-1322C incorporates advanced cooling technologies that enhance its operational efficiency. Its counterflow design is specifically engineered for improved airflow, ensuring optimal heat exchange. This design minimizes water loss through evaporation and enhances the cooling capacity, making it a cost-effective solution for cooling process water in industrial facilities.

Moreover, the model features low-noise fan operation. The low-noise axial fans are designed to provide efficient airflow while keeping sound levels to a minimum, making this unit ideal for applications in sound-sensitive environments. The fans are equipped with multiple speed settings, allowing operators to adjust performance based on cooling demands.

Another characteristic of the SPX Cooling Technologies 92-1322C is its ease of installation and serviceability. The modular design allows for quick assembly and disassembly, enabling efficient transport and installation. Additionally, the access panels and removable components facilitate regular maintenance and inspections, which are crucial for ensuring long-term operational effectiveness.

In terms of energy efficiency, the 92-1322C is equipped with a variable frequency drive (VFD) that optimizes fan speed based on real-time cooling requirements. This innovative technology not only reduces energy consumption but also leads to lower operational costs.

Overall, the SPX Cooling Technologies 92-1322C is a versatile and reliable cooling solution suitable for various industrial applications. Its combination of durability, advanced engineering, and energy-efficient features establishes it as a preferred choice for facilities looking to enhance their cooling operations while minimizing environmental impact.