Marley / Sigma Steel CoolingTower / Specifications: Base
Specifications | Specification Value |
15
4.0Fan Deck and Fan Cylinder:
4.1The fan deck shall act as a working platform for maintenance personnel. It shall be fabricated of no less than 12 gauge steel, and shall be designed for a uniform live load of 60 psf.
4.2Fan cylinders shall be molded FRP.
They shall be
5.0Mechanical Equipment:
5.1Fan(s) shall be
5.2Motor(s) shall be ____ hp maximum,
TEFC, 1.15 service factor, and specially insulated for cooling tower duty. Speed and electrical characteristics shall be 1800 (1800/900) RPM, single winding,
___ phase, ___ hertz, ___ volts.
■The indicated design values for framing and decking not only give you assurance that the tower can withstand long term operation in a hostile environment — but that it will accept many years of inspection and maintenance traffic by your operating personnel.
■
■
They should be readily adjustable to permit compensation for job site conditions that may tend to overload the motor. The fans of one manu- facturer require the purchase of special positioners for each increment of fan blade pitch.
Standard fan drives of other manufacturers may use
■Unless otherwise specified, motor speed will be 1800 RPM in 60 Hertz areas and 1500 RPM in 50 Hertz areas. If you prefer the operating flex- ibility of