SPX Cooling Technologies Marley Sigma Steel specifications Plan, Section

Models: Marley Sigma Steel

1 28
Download 28 pages 4.59 Kb
Page 8
Image 8
Plan

Marley / Sigma Steel CoolingTower / Engineering Data : Concrete Basin

8

6" MIN.

 

 

 

 

 

W IN TO IN OF BASIN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CASED ENDWALL FACE

Manual background 6" MIN.

6" MIN. 5"

 

AIRINLET FACE

 

PERL CELL

 

ANCHOR BOLTS

 

 

 

(SEE NOTE 5)

FACE

0"=

SUMP

 

 

 

INLET

AT 4'-

 

 

AIR

SPACES

 

 

 

A

 

CASED ENDWALL FACE

 

 

 

 

6" MIN.

5"

1'-6"

Plan

RECOMMENDED OPERATING WATER LEVEL

1'-0

Section

Tower

 

Dimensions

 

Operating Weight lb

Model

 

 

 

 

 

A

W

L

Single Fan Cell

Each Cell Add

 

 

 

 

 

 

 

121-111

3

23'-6"

12'-0"

25200

21525

 

 

 

 

 

 

122-111

4

25'-6"

16'-0"

32280

28430

 

 

 

 

 

 

123-111

4

27'-6"

16'-0"

33300

29080

 

 

 

 

 

 

124-111

5

27'-6"

20'-0"

39230

35025

 

 

 

 

 

 

125-111

5

31'-6"

20'-0"

42800

37715

 

 

 

 

 

 

126-111

6

31'-6"

24'-0"

48780

43910

 

 

 

 

 

 

127-111

7

31'-6"

28'-0"

54830

50550

 

 

 

 

 

 

NOTE

1Use this bulletin for preliminary layouts only. Do not use for construction. Obtain current drawings from your Marley sales representative. Concrete basin design and construction are by other contractors or purchaser.

2Operating weight is total wet operating weight of tower only, excluding water in concrete basin.

3Maintain at least 2'-0" of clear space at tower endwalls for construction purposes. Air inlet faces must have unobstructed air supply. If obstructions exist nearby, consult your Marley sales representative.

4Minimum basin depth is 1'-6". Basin depth may vary to suit your storage requirements.

5All anchor bolts complete with nut and washer must be furnished by others. Bolts must be 34" diameter with 112" all-thread projection.

6Other contractors or purchaser must design, locate, construct, and furnish sump(s) and overflow(s) to suit requirements. The sump(s) should be designed according to the pump manufacturer’s recommendations. Other design sources: ANSI/HI specifications 1.1-1.5 for centrifugal pumps, 2.1-2.5 for vertical pumps, and 9.8 for pump intake design.

Page 8
Image 8
SPX Cooling Technologies Marley Sigma Steel specifications Plan, Section