TWO TEMPERATURE - ONE HEATER HIGH TEMPERATURE STORAGE

WITH RECIRCULATION OF SANITIZING LOOP

NOTE 1: TOGGLE SWITCH CONTROLS 180°F (82°C) WATER CIRCULATION. INSTALL ON OR CLOSE TO DISHWASHING MACHINE. TOGGLE SWITCH MUST BE CLOSED (ON) DURING THE RINSE OPERATIONAND OPEN (OFF) WHEN DISHWASHER IS NOT OPERATING OR WHEN ON LONG STANDBY.

NOTE 2: INSTALLLINE TEMPERATURE CONTROL INAN UNINSULATED TEE BEYOND THE DISHWASHING MACHINE TAKEOFF IN THE SANITIZING LOOP. CONTROL SHOULD BE SET AT 185°F (85°C).

NOTE 3: ADJUST PLUG COCK SO THE SANITIZING LOOP FLOW RATE DOESNOTCAUSEUNNECESSARYTURBULENCEINTHETANK.

*TEMPERED WATER LOOP, IF USED, CONNECTTO POINT “A”.

**PIPE RELIEF VALVE TO OPEN DRAIN.

INSTALLIN ACCORDANCE WITH LOCAL CODES.

CAUTION: IF BUILDING COLD WATER SUPPLY HAS A BACKFLOW PREVENTER, CHECK VALVE OR WATER METER WITH CHECK VALVE. PROVISIONS FOR THERMAL EXPANSION OF WATER

IN THE HOTWATER SYSTEM MUST BE PROVIDED.

DANGER

TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES. SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 25. IF HIGHER PREHEAT TEMPERATURES ARE NECESSARYTO OBTAIN ADEQUATE BOOSTER OUTPUT, ADDANANTI- SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES.

14

Page 14
Image 14
State Industries SBN85390NE/A warranty