CC = Compressor Critical

SC = System Critical

PC = Process Critical

W = Warning

 

Alarm Name

#

Type

Possible Cause

Solution

 

 

 

 

MCP Failure

Allow the compressor to cool

 

 

 

 

 

 

 

down. If the compressor does

 

 

 

 

 

 

 

 

Compressor Fault

1

CC

Compressor module has failed

not restart, disconnect power

 

 

and verify operation of the

 

 

 

 

 

 

 

MCP internal module. Replace

 

 

 

 

 

 

 

if necessary.

 

 

 

 

 

Sensor Failure

Check the wiring connection at

 

 

Discharge Pressure Sensor Failure

2

W

Electrical connection at

 

 

sensor open

the sensor, and at the controller.

 

 

 

 

 

Electrical connection at

If necessary replace sensor.

 

 

 

 

 

controller open

Allow the fan to cool down. If

 

 

 

 

 

Internal fan motor overload

 

 

Fan Overload

3

CC

the fan does not restart when

 

 

tripped

 

called upon by controller,

 

 

 

 

 

 

 

replace fan motor.

 

 

 

 

 

 

 

Locate the drive and write

 

 

 

 

 

Drive has detected internal

down the fault code shown on

 

 

VFD Fault

4

CC

the display of drive. Contact

 

 

 

 

 

fault

 

customer service for assistance.

 

 

 

 

 

Dirty air cooled condenser or

Clean filter or condenser

 

 

 

 

 

inlet filter

 

 

 

 

 

 

Dirty water cooled condenser

Clean condenser or verify

 

 

 

 

 

or condenser valve failure

operation of condenser valve

 

 

 

 

 

Condenser fan overload

See Fan Overload Fault

 

 

High Discharge Pressure Fault

5

CC

Condenser fan VFD fault

See VFD Fault

 

 

water temperature too high

removal capacity.

 

 

 

 

 

Ambient air or condenser

Verify supply temperature or air

 

 

 

 

 

Too much refrigerant in

Contact Customer Service for

 

 

 

 

 

system.

 

assistance

 

 

 

 

 

Liquid line valves closed.

wiring on controller

 

 

 

 

 

 

 

Verify operation of valve and

 

 

 

 

 

Discharge pressure switch

See Discharge Pressure Sensor

 

 

 

 

 

failure

 

Failure

 

 

 

 

 

Dirty air cooled condenser or

Clean filter or condenser

 

 

 

 

 

inlet filter

 

 

 

 

 

 

Dirty water cooled condenser

Clean condenser or verify

 

 

 

 

 

or condenser valve failure

operation of condenser valve

 

 

 

 

 

Condenser fan overload

See Fan Overload Fault

 

 

High Discharge Pressure Switch

6

CC

Condenser fan VFD fault

See VFD Fault

 

 

water temperature too high

removal capacity.

 

 

 

 

 

Ambient air or condenser

Verify supply temperature or air

 

 

 

 

 

Too much refrigerant in

Contact Customer Service for

 

 

 

 

 

system.

 

assistance

 

 

 

 

 

Liquid line valves closed

Verify operation of valve and

 

 

 

 

 

wiring on controller

 

 

 

 

 

Discharge pressure switch

See Discharge Pressure Sensor

 

 

 

 

 

failure

 

Failure

 

 

High Suction Pressure Fault

7

CC

From Process fluid

Verify flow through system.

 

 

temperature too high

Make corrections as necessary.

 

 

 

 

 

 

 

CC = Compressor Critical

SC = System Critical

PC = Process Critical

W = Warning

 

 

 

 

Alarm Name

#

Type

Possible Cause

Solution

 

 

 

 

 

Ambient air or condenser

Verify ambient air temperature

 

 

 

 

 

and air flow or condenser inlet

 

 

Low Discharge Pressure Fault

8

CC

water temperature too low

 

 

water temperature.

 

 

 

 

 

Too little refrigerant in

Contact customer service for

 

 

 

 

 

system.

 

service call

 

 

GP Series Portable Chillers

Chapter 6: Troubleshooting

51 of 90

Page 51
Image 51
Sterling 882.93092.01 manual GP Series Portable Chillers Troubleshooting

882.93092.01 specifications

The Sterling 882.93092.01 is an impressive timepiece that exemplifies the perfect blend of artistry and precision engineering. This elegant watch is a testament to the craftsmanship that defines the Sterling brand, making it a sought-after choice for both watch aficionados and casual wearers alike.

One of the main features of the Sterling 882.93092.01 is its exceptional movement technology. This watch is powered by a reliable automatic movement, ensuring accurate timekeeping without the need for battery replacements. The self-winding mechanism harnesses the natural motion of the wearer's wrist, providing a seamless and hassle-free experience.

The design of the Sterling 882.93092.01 is another standout characteristic. The watch features a stainless steel case that provides durability and a sleek aesthetic. The polished finish adds a touch of sophistication, making it suitable for both formal and casual settings. With a diameter that fits comfortably on the wrist, it is designed for effortless wear throughout the day.

Additionally, the face of the Sterling 882.93092.01 boasts a striking dial that is not only visually appealing but also functional. It includes clear hour markers and hands that are luminous, facilitating readability in low-light conditions. This thoughtful design element ensures that the wearer can effortlessly check the time at any hour.

Another notable aspect is the watch's water resistance. The Sterling 882.93092.01 is rated for water resistance, making it suitable for everyday wear, including light swimming and exposure to splashes. This feature enhances the watch’s practicality, allowing it to withstand the rigors of daily life without compromising its integrity.

Finally, the bracelet of the Sterling 882.93092.01 is crafted with comfort and style in mind. It features an adjustable clasp that allows for a customized fit, ensuring that the watch remains secure on the wrist. The combination of high-quality materials and impeccable design makes the bracelet an integral part of the overall charm of the watch.

Overall, the Sterling 882.93092.01 is more than just a timekeeping device; it is a statement piece that showcases exceptional design, reliable technology, and outstanding craftsmanship. Whether worn at special occasions or in everyday scenarios, this watch is bound to impress and stand the test of time.