Roberts Gorden 350, 200, 150, 400, 250, 300, 225 TROUBLESHOOTING 13.1 General, Explosion Hazard, Start

Models: 175 225 300 250 400 150 350 200

1 48
Download 48 pages 52.86 Kb
Page 33
Image 33
SECTION 13: TROUBLESHOOTING 13.1 General

SECTION 13: TROUBLESHOOTING

SECTION 13: TROUBLESHOOTING 13.1 General

Start WARNING

Explosion Hazard

Installation must be done by a registered installer/ contractor qualified in the installation and service of gas-fired heating equipment or your gas supplier.

Failure to follow these instructions can result in death, injury or property damage.

Start

Are gas & electrical

supplies on?

Yes

Does axial fan run

immediately upon supplying

power to heater?

No

Is ignition control showing a

"2 flashes" led code?

No

Does the combustion

fan run?

Yes

With external controls (i.e. thermostat) on, does the burner continue through the heating cycle?

Yes

Heater Operating

TROUBLESHOOT ENDS.

No

Yes

Yes

No

No

No

Turn on supplies.

Wait 10-15 minutes for limit switch to cool. Does fan Yes

stop running?

No

Replace temperature

limit switch.

Burner has locked out due

to ignition failure. Use

Troubleshooting for Automatic

Ignition Burner Systems section to test burner.

Use Troubleshooting for

Combustion Fan section to

test fan.

Has burner “Locked Out”? No

Yes

Use Troubleshooting for Automatic Ignition Burner Systems section to test burner.

If problems persist, contact

Roberts-Gordon, LLC at

www.rg-inc.com

Fan and limit switch are

operating normally.

The limit switch has

 

 

tripped. See Manual Reset

No

Replace limit switch.

Limit Switch Figure.

 

 

Yes

Ensure proper air flow clearance for axial fan. Open louvers slightly.

Replace axial fan if it does

not operate.

27

Page 33
Image 33