SECTION 6: VENTING
6.7 Vent Material
Vent material may be single wall 26 ga. (minimum) galvanized steel or equal thickness stainless steel. Completely seal all joints, refer to Page 7, Section 6.2.
If penetrating a combustible wall or roof, a listed thimble with 2" (5 cm) clearance must be used. Where local codes permit, a single section of type
Figure 3: Vent and Roof Detail
Vent |
|
Terminal |
|
| Flashing |
| or Rain Collar |
Roof |
|
| Listed Thimble |
2" Air Gap to | Vent |
| |
Combustible Material |
|
Figure 4: Standard Vented Heater - Vertical and Horizontal Vent Termination
Vent Terminal
Flashing
(By Others)
Listed
Thimble
(2" Clearance)
4" Dia.Vent |
| Listed |
|
Vertical | 90° | Thimble | |
(2" Clearance) | |||
Option | Bend | Flashing | |
| Horizontal | ||
| (By Others) | ||
| Option |
|
|
| Vent |
| Vent |
|
|
| |
|
|
| Terminal |
| Condensate | 12" (31 cm) | Note: Vent supports |
| Minimum | ||
| Trap to Drain |
| not shown. |
| (Optional) |
|
|
Model | Vent Diameter | Part Number |
UHA 150 - 400 | 4" (10 cm) | 90502102 |
9