SECTION 5: MAJOR COMPONENTS 5.1 General

COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL

SECTION 5: MAJOR COMPONENTS 5.1 General

Heaters are designed for installation above 6'

(1.8 m). These heaters must be installed within the heated space. Duct delivery systems are not permitted with axial fan units. When handling or supporting the heater from below, ensure that the weight is taken at the support points.

5.2 Suspension

5.2 Suspension WARNING

Crush Hazard

Use 3/8" threaded rod minimum.

Failure of the supports can result in death, injury

or property damage.

For typical suspension, See Page 6, Figure 2.

Figure 2: Suspension Methods

Unistrut Figure 2: Suspension Methods Channel Nut

Washer Manual backgroundManual background

Nut

3/8"

Threaded

Rod

3/8" Threaded Rod Manual background

Nut

Washer Manual backgroundManual background

Riv

Nut

Ensure all suspension hardware is torqued to a minimum of 20 ft lbs.

Support Points

Cone Point

Set Pin

Window

Clamp

UnistrutManual background