Roberts Gorden 200 Burner Observation, Window, Combustion Fan Scroll, Wheel and Motor, Orifices

Models: 175 225 300 250 400 150 350 200

1 48
Download 48 pages 52.86 Kb
Page 32
Image 32
Burner Observation

COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL

Burner Observation

Make sure it is clean and free of cracks or holes.

Window

Clean and replace as required.

 

 

 

Combustion Fan Scroll,

Compressed air or a vacuum cleaner may be used to clean dust and dirt.

Wheel and Motor

 

 

 

Inshot Burners and

Clear of obstructions (even spider webs will cause problems).

Orifices

Carefully remove any dust and debris from the burner.

 

 

 

Direct-Spark Igniter

Replace if there are cracked ceramics, excessive carbon residue, or erosion

 

of the electrode.

 

The electrode gap should be 1/8" (3.2 mm).

 

 

Thermostat

There should be no exposed wire or damage to the device or wiring.

 

See Page 19, Section 10.

 

 

Suspension Points

Make sure the heater is hanging securely.

 

Look for signs of wear on the suspension materials or ceiling.

 

See Page 6, Figure 2.

 

 

Silicone Tubing

Ensure tight, secure fit on all pressure fittings at pressure switch,

 

burner partition, and blower outlet.

 

 

Gas Valve

Verify that cap covering pressure regulator adjustment screw is secure and

 

has not been tampered with.

 

Verify all wiring connections.

 

 

Condensate Drain

Flush drain and clear any obstructions.

(when installed)

 

 

 

26

Page 32
Image 32
Roberts Gorden 200, 350 Burner Observation, Window, Combustion Fan Scroll, Wheel and Motor, Inshot Burners and, Orifices