Installation Overview
3-2 Firs t Edition 96047
Rear Door Replacement
Some early model library rear doors are not compatible with the optional rack
cooling feature. Check the serial number of your library, if it falls within the
ranges listed, you need to replace the rear door.
The following table lists the serial number range, description, and field bill
number for the rear door.
Power Connections
Make sure you have the correct power connections for this feature:
•The L180 library, UPS Model SU1400RM2U, uses an L5-15, locking 120 VAC,
15 Amp plug. The customers power source requires an L5-15R receptacle.
•The L700 library, UPS Model SU3000RM3U, uses an L5-30, locking 120 VAC,
30 Amp plug. The customers power source requires an L5-30R receptacle.
•The International feature (EPWR) uses a Hubbell 316P6W (plug) and
Hubbell 316R6W (receptacle).
■Before Beginning
Before beginning these installations, make sure:
•You observe the information in “Safety Precautions” on page x.
•All equipment has been received.
•There are two separate power sources; one for each UPS.
•The library and all tape drives are offline.
Note: For simplicity, this installation procedure uses figures of the L180 UPS;
the procedure is similar for the L700. Refer to the instructions sent with
the feature for specific information about how to install the UPS.
Library Serial
Numbers
Description Field Bill
L180 1 - 6015 StorageTek rear door
HP rear door
Sun rear door
NCR rear door
101334
101336
101337
101338
L700 1 - 6798 StorageTek rear door
HP rear door
NCR rear door
101326
101339
101340