96047 First Edition 4-7
Fault Isolation
Troubleshooting the UPS
Table 4-1 describes some possible problems and solutions when
troubleshooting the UPS:
Table 4-1. Troubleshooting the APC Uninterruptible Power Supply
Problem and Possible Cause Solution
UPS will not turn on.
ON button not pushed. Press the ON button once to power on the UPS
and other equipment.
UPS not connected to AC power
supply.
Make sure the power cable from the UPS to the
customers input power is securely connected at
both ends.
UPS input circuit breaker tripped. Reduce the load on the UPS by unplug ging
equipment and reset the circuit breaker (on back
of the UPS) until you isolate the device causing the
problem (or the UPS).
Very low or no utility voltage. Check the AC power supply to the UPS with a
table lamp. If the light is very dim, check the input
voltage.
Battery not connected properly. Check the battery connections.
UPS will not turn off.
Internal UPS fault. Do not attempt to use the UPS. Unplug the UPS
and contact StorageTeks Customer Support
Services* immediately to obtain a new UPS.
UPS operates on battery although norma l line voltage exists.
UPSs input circuit breaker tripped. Reduce the load on the UPS by unplugging
equipment and reset the circuit breaker (on back
of the UPS) until you isolate the device causing the
problem (or the UPS).
Very high, low, or distorted line
voltage.
Move the UPS to a different outlet on a
different circuit.
Test the input voltage with the Utility Voltage
display. If acceptable to the load, reduce the
UPSs sensitivity (refer to the APC Users
Manual for more information).
UPS beeps occasionally.
Normal UPS operation. None. The UPS is protecting the load.