Steca Xtender

Installation and Operating Instructions 723.932 Xtender V0.511 Seite 37

15 Technical data

Model XTH 3000-12 XTH 5000-24 XTH 6000-48 XTH 8000-48

Inverte
r
Rated battery voltage 12 V 24 V 48 V 48 V
Input voltage range 9.5 - 17 V 19 - 34 V 38 - 68 V 39 - 68 V
Continuous power @ 25 °C 2,500 VA 4,000 VA 5,000 VA 7,000 VA
Smart boost power 2,500 VA 4,000 VA 5,000 VA 7,000 VA
30 minute charge @ 25 °C 3,000 VA 5,000 VA 6,000 VA 8,000 VA
5 second charge @ 25 °C 3 x Pnom
Maximum charge Up to short-circuit
Maximum asymmetrical charge Up to Pnom
Load detection (standby) 2 to 25 W
Admissible cos phi 0.1 – 1
Maximum efficiency 93% 94% 96% 96%
Open-circuit power
OFF/standby/ON 1.7 W/2.2 W/14
W 1.8 W/2.5 W/20
W 2.2 W/3 W/22 W 2.2 W/3.8 W/34
W
Output voltage 230 Vac (-10% /0)
Output frequency 50/45-65 Hz +/- 0.05% (quartz-controlled)
Harmonic distortion <2%
Dynamic correction 0.5 ms (charge leap from 0 to 100%)
Overcharge and short-circuit Automatic disconnection then 2 startup attempts
Overheating protection Alarm prior to disconnection and automatic restart
Battery charge
r
6-phase battery charger Programmable I-U-Uo-equalisation-Uo(low)-U(periodic)
Adjustable charge current 0 - 160 A 0 - 140 A 0 - 100 A 0 - 120 A
Input current sharing system 1 - 30 A 1 - 50 A
Maximum input voltage 265 Vac
AC input voltage range Level of detection adjustable from 150 to 230 Vac
Admissible input frequency 45 - 65 Hz
(PFC) EN 61000-3-2
Battery control (factory value / adjustable range with RCC-02)
End of absorption by duration 4 / 0.25 - 10 h or by current - / 4 - 30 A
Absorption voltage 14.4 / 9.5 - 18 V 28.8 / 19 - 36 V 57.6 / 38 - 72 V
Periodic absorption voltage - / 9.5 - 18 V - / 19 - 36 V - / 38 - 72 V
Maintenance voltage 13.6 / 9.5 - 18 V 27.2 / 19 - 36 V 54.4 / 38 - 72 V
Reduced maintenance voltage - / 9.5 - 18 V - / 19 - 36 V -- / 38 - 72 V
Equalisation
End of equalisation
Equalisation voltage - / 9.5 - 18 V - / 19 - 36 V - / 38 - 72 V
10.8 / 9.5 - 18 V 21.6 / 19 - 36 V 43.2 / 38 - 72 V
- / 0 - 32 days
- / 0 - 10 hours
Temperature compensation -5 / 0 to-8 mV/°C/cell (optional BTC-01)
G
eneral data
Auxiliary contacts 2 independent contacts 16 A - 250 Vac (potential-free 3 points)
Maximum transfer relay current 30 A 50 A
Maximum transfer time <25 ms
Weight 34 kg 40 kg 42 kg 46 kg
Dimensions: H x W x D [mm] 220x290x500 220x310x500
Protection degree IP23
Conformity EN 61000-6-1, EN 61000-6-3, EN 55014, EN 55022, EN 61000-3-2,
Dir. 89/336/EEC, LVD 73/23/EEC
Operating temperature range -20 to 55 °C
Ventilation Forced from 45 °C
Noise level <35 dB / <50 dB (without / with ventilation)
Warranty 2 years
Options
Battery temperature sensor : BTS-01
Remote control and programming centre: RCC-02 / RCC-03