Pilot
Orifice
Figure 29
Step 6. All Millivolt Systems – Attach manometer to the manifold side pressure test fitting and verify manifold pressure reads 3.5 inches water column (0.87 kPa) for natural gas, and 10.0 inches water column (2.49 kPa) for propane gas.
Step 7. Refer to Figure 29 and remove the pilot hood assembly to access the hexed pilot orifice. Remove and replace the orifice with the one provided with the kit.
Electronic Appliances
Step 8. Honeywell Electronic Valves - See Figure 31 and the instructions provided with the kit. Remove the slotted cap screw,
3.5inches water column (0.87 kPa) for natural gas, and 10.0 inches water column (2.49 kPa) for propane gas.
CONTROL | Inlet Pressure Test Port |
OFF ON | |
| I |
ETINGI |
|
| ISP |
Manifold
Pressure
Test Port
Slotted
Cap
Spring
Adjusting
Screw
Figure 31
See Figure 30 and replace the pilot orifice as follows: Remove the ignitor assembly retainer clip, and carefully remove the ignitor assembly.
Exercise extreme care to prevent damage to or breakage of the ignitor assembly. Remove the screw securing the pilot assembly to its mounting bracket. Back off the flare nut at the end of the pilot gas line to free the pilot assembly from the gas line. Remove the pilot orifice and replace it with the one provided with the conversion kit. Reinstall the pilot assembly by reversing the steps detailed here.
When reinstalling the ignitor assembly, use extreme care to prevent damage and break- age. Do not apply any leverage to the ignitor assembly while restoring the retainer clip to its original position.
All Models
Step 9. Unscrew the orifice from the manifold and replace it with the one provided with the kit, #49 (0.073) for natural gas units and (0.045) for propane (Figure 32 ).
Figure 32
Pilot Assembly
Step 10. Reassemble all removed components by reversing the procedures outlined in the preceding steps. Use pipe joint compound or Teflon tape on all pipe fittings before installing (ensure propane resistant compounds are used in propane applications, do not use pipe
Pilot Orifice
Ignitor
Assembly
Retaining
Clip
joint compounds on flare fittings).
Step 11. Attach apropriate conversion kit label (Figure 33 ) to the rating plate on the appliance.
THIS APPLIANCE HAS BEEN CONVERTED TO:
NATURAL GAS
Flare Nut
Note: If the ignitor assembly is damaged, a replacement kit is available, order Catalog Number 87L54.
Figure 30
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
INPUT BTU/HR – 15,000
MANIFOLD PRESSURE – 3.5"
ORIFICE SIZE – #49 (0.073)
THIS APPLIANCE HAS BEEN CONVERTED TO:
PROPANE/LPG
INPUT BTU/HR – 15,000
MANIFOLD PRESSURE – 10"
ORIFICE SIZE – (0.045)
Figure 33
Step 12. Turn on gas supply and test for gas leaks.
13