
Note: Supply wires may be alternatively connected to the outlet using the screw terminals, however the black supply wire must be wired to a terminal that is opposite (across the outlet) the point where the white supply wire is connected.
Ground Wire
Connection
White (Supply)
120 Vac
60 Hz
| Bipolar |
Black | Terminal |
(Supply) | Screw |
Figure 16
Gas Flex Line (provided) | Gas Valve |
| (Millivolt or |
¹₂" x ³₈" Flare | Electronic) |
| |
|
³₈" Flex Tubing |
|
| ³₈" NPT Flare |
| Fitting (Remove |
Alternate “Hard Piping” | Before Hard |
Piping) | |
(may be required in some areas, consult local codes.) |
|
³₈" Nipple
³₈" Union
Gas Stub
³₈" Close Nipple
³₈"
¹₂" x ³₈" Reducer
Note: ¹₂" NPT At Inlet Of Gas Valve For Electronic Models.
Figure 17
8 | NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. |
D. When the gas lines are tested and leak free, observe the individual tongues of flame on the burner. Make sure all ports are open and producing flame evenly across the burner. If any ports are blocked, or partially blocked, clean out the ports.
Step 7. Installing Outside Air Kit – These appliances are equipped with an outside
After completing the installation of the optional combustion air vent system the actuator arm must be put in service and tested to ensure proper operation before completing any enclosure around the firebox. Failure to do so may result in extensive and costly rework.
WARNING: DO NOT REMOVE THE ACTUATOR ARM LOCKING SCREW UNLESS THE COMPLETE OUTSIDE AIR VENT SYSTEM HAS BEEN INSTALLED IN ACCORDANCE WITH THE DETAILED INSTRUCTIONS PROVIDED WITH THE KIT.
Locate the actuator arm along the right side of the appliance firebox opening and refer to Figure 18. After completing the installation of the Outside Combustion Air Kit remove and discard the actuator arm locking screw.
Outside Air
Actuator
Remove Locking Screw and “Pop” Actuator to the Left Before Initial Use
Pull Forward to Open,
Push Back to Close
Figure 18